It is also possible to program the value M at LED A or LED B. In that case the LED will burn as long as
there is at least one section armed.
All possible values can be found in the figure below:
Output: Possible
values:
Function:
LED OK
A, B, C, D, E, F, G
or H
The LED lights when all zones but the delayed zones belonging
to the programmed section are closed. When an instant or 24
hour zone is opened, this LED is off. When only a delayed zone
is opened and all other zones are closed, the LED flashes.
LED OK
T
The LED lights when all zones but the delayed zones in the entire
system are closed.
LED A
LED B
A, B, C, D, E, F, G
or H
The LED lights when the section is armed.
LED A
LED B
M
The LED lights when there is at least one section armed. This
value shows that not the entire system is disarmed.
LED A
LED B
T
The LED lights when all sections are armed.
BUZZER
A, B, C, D, E, F, G
or H
The buzzer is activated during the entry and exit delays of one of
the delayed or follower zones in the programmed section. The
buzzer function is also dependant on the programmed setting in
screen 8 “buzzer during entry/exit time”.
BUZZER T
The buzzer is activated during the entry and exit delays of one of
the delayed or follower zones in the entire system. The buzzer
function is also dependant on the programmed setting in screen 8
“buzzer during entry/exit time”.
SCREEN 8
INSTALLATIONS DATA: ALPHAVISION NG v1.1 -- date
OUTPUT TIME DELAY-TIME
Alarm on LCD if CP ARMED : J
Output 1: 003 000
Aut. turn off bac LED's: N
Output 2: 003 000
F22 instantly accessible with #: N
Output 3: 003 000
Duress message enabled : N
Output 4: 003 000
* + # keycombination enabled : N
Output 5: 003 000
Alarm after 6x wrong code : N
Output 6: 003 000
Arm/disarm in historical log : J
Output 7: 003 000
Testmessage in historical log : J
Output 8: 003 000
Buzzer during entrytime : J
Siren 9: 003 000
Buzzer during exittime : N
Slow-whoop 9: 060 000
Buzzer during walktest : J
L.S. during walktest : J
Keyswitches are PULSE contacts : J
Safe zone alarm if >. min. disarmed: 015
Medical instead of technical : N
Number of minutes prealarm RTC(0-9): 5
"Final door" function enabled : N
Auto-reset (1-9): 3
A+B function (Robofon DK) : N
Number of digits usercodes (4-6): 6
Supervision without tamper (WI): N
Tel. linemonitor alarm aft. . x3sec: 001
Delaytime mains failure (minutes): 030
Installercode : 123456
Name of the installingcompany : Alphatronics BV_
At
output time
the activated times for each output of the control panel and the I/O and input + 8 OC
modules are programmed. This time is programmed in minutes (0 to 255 minutes). When the programmed
time has passed, the output will automatically be deactivated. Also when a section is disarmed, all outputs
will be deactivated.
AlphaVision NG installation manual Rev. 2.0 27-08-2003 Blz. 46/101