6.5 DC output connections - bulk distribution
WARNING!
Do not complete the final live connections to the battery. Leave open and insulate the final
connections or remove the battery fuses. Switch off the battery contacts if used.
The DC output wire must be UL approved XHHW or RHH/RHW (for Canadian users RW90; for European users,
must be EN or IEC approved wire). Control and sense wires must be UL approved 1015 (for Canadian users TEW
type; for European users, must be EN or IEC approved wire).
If the systems is operating in a floating output then no reference or common ground is required to be connected
to the power system. If the system is intended to operate in a common bond network than the common output leg
must be connected to ground.
Typical locations for connecting reference ground:
1. Battery termination bar
2. Common return bar on the distribution
3. Connection on the back of the 2.4kW / 3.0kW shelf
The 23 inch and 19 inch bulk distribution models have positive and negative output bars.
Figure 8 —
Positive and negative output bars on 23 inch and 19 inch bulk distribution models
POSITIVE (+)
OUTPUT BAR
NEGATIVE (-)
OUTPUT BAR