Battery Top Terminal Mount
Battery Top Terminal Mount
4.3.1
4.3.1
Termination Bus Assembly
Termination Bus Assembly
ENSURE BATTERY STRING IS NOT COMPLETELY
CONNECTED IN SERIES PRIOR TO THE
INSTALLATION OF THE DCX UNIT FOR SAFETY
PURPOSES. DISCONNECT SEVERAL SERIES BUS
CONNECTIONS OF THE STRING TO ENSURE THE
TOP NEGATIVE TERMINAL IS NOT CONNECTED
TO THE REST OF THE STRING SO THAT THE
INSTALLATION WORK CAN BE DONE SAFELY
WITHOUT VOLTAGE PRESENT. ENSURE THAT
ALL THE PLASTIC CELL TERMINAL COVERS ARE
INSTALLED TO PREVENT ACCIDENTAL CONTACT OR
SHORT CIRCUIT OF THE STRING TERMINALS WITH
TOOLS ETC. DURING THIS INSTALLATION PROCESS.
CAUTION!
The DCX unit ships without the battery termination bus installed and
will require assembly. The termination bus hardware comes pre-
installed on the DCX and requires removal before terminal plate can
be installed. Follow the steps below for termination bus installation
instructions.
Step 1.
Flip up the front hinged lid, then remove the lexan breaker
cover by removing the phillips-head screws as shown in Fig.
3.
Step 2.
Remove the 3/8 in. socket head cap hardware from the
bottom of the circuit breaker as shown in Fig. 4.
Step 3.
Remove the three pre-installed phillips-head screws from the
glastic isolators as shown in Fig. 5.
Step 4.
Insert the termination plate into the slot located on the
bottom of the DCX battery disconnect chassis as shown in
Fig. 6.
Step 5.
Reinstall the three phillips-head screws into the glastic
isolators from Step 3.
Step 6.
Reinstall the 3/8 in. socket head cap hardware into bottom of
the circuit breaker from Step 2 (recommended torque value:
225 in-lbs). Ensure the ring terminal (blue wire) on the
furthest breaker pole to the right is secured between the 3/8
in. socket head cap screw hardware and the DCX
termination plate as shown in Figure 7.
Table 3.
Termination Plate Torque Specifications
TERMINATION
TYPE
HOLE/
STUD SIZE
RECOMMENDED TORQUE
VALUE
Threaded Insert
3/8 in.
18.75 ft·lbs
Step 7.
Reinstall the lexan breaker cover from Step 1 by reinstalling
the phillips-head screws.
Step 8.
Close the hinged lid.
Figure 3.
Lexan breaker cover
Figure 4. 3/8 in. socket head hardware
Figure 5. Phillips head screws
Figure 6.
Termination Bus
Figure 7. Reinstall socket head hardware