Battery Top Terminal Mount

Battery Top Terminal Mount

4.3.1 

4.3.1 

Termination Bus Assembly

Termination Bus Assembly

ENSURE BATTERY STRING IS NOT COMPLETELY 

CONNECTED IN SERIES PRIOR TO THE 

INSTALLATION OF THE DCX UNIT FOR SAFETY 

PURPOSES. DISCONNECT SEVERAL SERIES BUS 

CONNECTIONS OF THE STRING TO ENSURE THE 

TOP NEGATIVE TERMINAL IS NOT CONNECTED 

TO THE REST OF THE STRING SO THAT THE 

INSTALLATION WORK CAN BE DONE SAFELY 

WITHOUT VOLTAGE PRESENT. ENSURE THAT 

ALL THE PLASTIC CELL TERMINAL COVERS ARE 

INSTALLED TO PREVENT ACCIDENTAL CONTACT OR 

SHORT CIRCUIT OF THE STRING TERMINALS WITH 

TOOLS ETC. DURING THIS INSTALLATION PROCESS.

CAUTION!

The DCX unit ships without the battery termination bus installed and 

will require assembly. The termination bus hardware comes pre-

installed on the DCX and requires removal before terminal plate can 

be installed. Follow the steps below for termination bus installation 

instructions.

Step 1. 

Flip up the front hinged lid, then remove the lexan breaker 

cover by removing the phillips-head screws as shown in Fig. 

3.

Step 2. 

Remove the 3/8 in. socket head cap hardware from the 

bottom of the circuit breaker as shown in Fig. 4.

Step 3. 

Remove the three pre-installed phillips-head screws from the 

glastic isolators as shown in Fig. 5.

Step 4. 

Insert the termination plate into the slot located on the 

bottom of the DCX battery disconnect chassis as shown in 

Fig. 6.

Step 5. 

Reinstall the three phillips-head screws into the glastic 

isolators from Step 3.

Step 6. 

Reinstall the 3/8 in. socket head cap hardware into bottom of 

the circuit breaker from Step 2 (recommended torque value: 

225 in-lbs). Ensure the ring terminal (blue wire) on the 

furthest breaker pole to the right is secured between the 3/8 

in. socket head cap screw hardware and the DCX 

termination plate as shown in Figure 7.

Table 3. 

Termination Plate Torque Specifications

TERMINATION 

TYPE

HOLE/

STUD SIZE

RECOMMENDED TORQUE 

VALUE

Threaded Insert

3/8 in.

18.75 ft·lbs

Step 7. 

Reinstall the lexan breaker cover from Step 1 by reinstalling 

the phillips-head screws.

Step 8. 

Close the hinged lid.

Figure 3. 

Lexan breaker cover

Figure 4.  3/8 in. socket head hardware

Figure 5.  Phillips head screws

Figure 6. 

Termination Bus

Figure 7.  Reinstall socket head hardware

Summary of Contents for C016-1001-10

Page 1: ...DCX Series Top Terminal Battery Disconnect System Installation and Operation Manual Effective January 2021...

Page 2: ...rovides fumes safety information to PREVENT INJURY OR DEATH to the technician or user WARNING FUMES HAZARD FIRE HAZARD WARNING provides flammability safety information to PREVENT INJURY OR DEATH to th...

Page 3: ...system please contact Alpha Technologies Services Inc or your nearest Alpha representative Alpha shall not be held liable for any damage or injury involving its enclosures power supplies generators b...

Page 4: ...cuit Overloading 7 4 2 5 Reliable Earthing 7 4 2 6 Disconnect Device 7 4 3 Battery Top Terminal Mount 8 4 3 1 Termination Bus Assembly 8 4 3 2 Battery Top Mounting Brackets 9 4 4 Chassis Ground 10 4 5...

Page 5: ...art numbers refer to Section 6 on Page 17 2 0 2 0 Theory of Operation Theory of Operation The DCX disconnect product family includes multiple amperage ratings and installation mounting schemes to prov...

Page 6: ...otification within 24 hours of delivery of any shipping damage in order to cover the cost of the damage via repair or replacement It is the responsibility of the recipient to inspect the shipment imme...

Page 7: ...ment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised 4 2 3 4 2 3 Mechanical Loading Mechanical Loading Mounting of the equipment in...

Page 8: ...y removing the phillips head screws as shown in Fig 3 Step 2 Remove the 3 8 in socket head cap hardware from the bottom of the circuit breaker as shown in Fig 4 Step 3 Remove the three pre installed p...

Page 9: ...ackets will require finger tight installation onto the DCX to properly allow marking for self tapping screw locations EnerSys C D GNB mounting bracket kits or for 1 4 in X 20 threaded insert locations...

Page 10: ...in lbs Step 7 After mechanical mounting of DCX unit has been completed snap the two black plastic hole plugs into the access holes that cover the 3 8 in mounting bolts see Figure 13 4 4 4 4 Chassis Gr...

Page 11: ...ch function disabled via a slide switch located on the circuit board see Figure 16 Slide this switch to the enabled position if the EPO function is desired 4 7 4 7 Alarm Contacts Alarm Contacts The DC...

Page 12: ...HAZARD MAKE SURE THAT ALL FEEDER CABLES HAVE HEAT SHRINK APPLIED PRIOR TO TERMINATION AND THAT NO OXIDE COMPOUND IS APPLIED TO ALL COPPER TO COPPER CONNECTIONS SEE SECTION 5 FOR TERMINAL SPECIFICATION...

Page 13: ...ith the plastic safety covers preinstalled These covers will require removal to allow access to the inside of the unit during cable installation It is important that all plastic covers have been reins...

Page 14: ...0A CONNECTIONS Communications Battery Positive Terminal block 14 16 AWG Output Termination 1 2 in Threaded insert 1 75 in CTC 4 positions 3 8 in Threaded insert 1 in CTC 3 positions Chassis Ground 1 4...

Page 15: ...P50 17 3X8 DDmP50 17 C016 2314 10 DCX Mount Kit EnerSys DDmP50 17 4X6 DDmP50 17 C016 2300 10 DCX Mount Kit EnerSysDDmP85 15 4x6 DDmP85 15 C016 2320 10 DCX Mount Kit EnerSys DDmP85 21 3X8 DDmP85 21 C01...

Page 16: ...00A25 100A27 C016 228 10 Table 14 Battery Mounting Bracket Kits For East Penn Manufacturing Batteries Interlocking DESCRIPTION APPLICABLE BATTERY SYSTEM PART NUMBER DCX Mount Kit Unigy 95 17 to 95 27...

Page 17: ...17 C048 699 30 R03 Rev B 01 2021 Appendix A Appendix A Mechanical Drawings Mechanical Drawings A 1 A 1 DCX Battery Disconnect Isometric View DCX Battery Disconnect Isometric View...

Page 18: ...18 C048 699 30 R03 Rev B 01 2021 A 2 A 2 DCX Battery Disconnect Dimensions DCX Battery Disconnect Dimensions...

Page 19: ...19 C048 699 30 R03 Rev B 01 2021 A 3 A 3 DCX Chassis Ground Locations DCX Chassis Ground Locations...

Page 20: ...20 C048 699 30 R03 Rev B 01 2021...

Page 21: ...21 C048 699 30 R03 Rev B 01 2021...

Page 22: ...Technical Support 1 800 863 3364 For more information visit our website at www alpha com 2021 Alpha Technologies Services Inc All Rights Reserved Trademarks and logos are the property of Alpha Techno...

Reviews: