0370260-J0 Rev B
5.1.
Overview Display
The following web page will be displayed when the RBMS Plus is connected to the batteries with the standard battery
harness.
The
Voltage from Battery Cable
displays the string voltage. Alarms may be provisioned for this voltage by pressing the
associated
A
button. This is also the voltage powering the RBMS Plus
The voltage for each battery is displayed. Alarms may be provisioned for this voltage by pressing the associated
A
button.
The web page also displays values for
Temperature
,
Line Voltage
(w/optional WT-5 transformer),
AC Current
(w/optional PBT-PA-CS-1 current probe),
Moisture Sensor
(w/optional PBT-PA-MS-1 sensor), and the status of the two
Auxiliary
Input
general purpose inputs. Pressing the
A
button next to a parameter allows configuring alarm settings for
that parameter.
The AC
Current Reading
will appear when there is an optional current sensor cable connected to the RBMS Plus. If a
sensor is not connected the reading will display “0.00 AC Amps”. Alarms may be provisioned for this parameter by
pressing the associated
A
button.
Pressing the
Site Setup
button displays the menu to edit the Site Setup Display text names, set the admittance
measurement interval, discover / reset sensors, flash the power to the modem and log off.