Type the IP address of the RBMS Plus in the browser’s URL address space, for example “50.199.84.xxx”. The controller
will serve the intial web page which lists all battery strings discovered, their total string voltage and their status. On the
bottom left hand corner of the web page you will see text which toggles between “Updated” and “Connected”. This
indicates normal operation. However, if you see the message “Trying to Connect” or “Unable To Connect” you may
have problems with a firewall or router blocking UDP port 30704. Contact your IT department for assistance.
The time displayed at the lower right of each web page is the PC time, not
the RBMS Plus time.
In each of the web pages, any display field that has user-definable alarm settings associated with it will display
a button with an
A
inside it next to the field. Fields with other settings will display a button with an
S
. Clicking
on the button will display a web page with the settings.
Clicking on the buttons above will require entry of a password created in the Telnet password setup screen. There are
two web passwords, Web password 1 is for user access that will allow the operator to only view alarm thresholds and
not make changes. Web password 2 is for admin access and will allow changes to alarm thresholds and site setup
configurations.
5.
The following sections show the various web pages on the RBMS Plus. The content of these pages will vary depending
on if options are installed such as sensors, current sensor, moisture sensor and line voltage sensor.