7.4
Factory Ranges and Defaults
The following table lists the rectifier settings/ranges/defaults; changes are made via the CXC:
Setting
Range (minimum to maximum)
Default
Float (FL) Voltage
23.75 – 29.1V
27V
Equalize (EQ) Voltage
24.9 – 30.1V
27.5V
Battery Test (BT) Voltage
22 – 26V
23V
OVP
See note below – 31.5V
28.5V
Current Limit (CL)
23 – 100%
100%
Power Limit (PL)
0 – 100%
100%
Module Start Delay
0 – 250s
1s
System Start Delay
0 – 600s
0s
Low Voltage Alarm (LVA)
21 – 26V
22V
High Voltage Alarm (HVA)
26 – 31.5V
27.75V
EQ Timeout
1 – 2399h
30h
BT Timeout
1 – 250h
8h
Softstart Ramp-rate
Normal/Fast
Normal
CL/PL Alarm
Enable/Disable
Enable
Remote Shutdown
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
Table D–Cordex 24-3.1kW factory ranges and defaults
NOTE:
OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 25.7V.