MODEL
ITEM
CONTINUITY
PLUS-1K
CONTINUITY
PLUS-2K
CONTINUITY
PLUS-3K
Output
Overload Capacity
(
tolerance±1%
)
Line Mode:
<105% continuous
106-120% for 30 seconds transfer to bypass.
121-150% for 10 seconds transfer to bypass.
>150% Immediately transfer to bypass.
Buzzer continuously alarms.
Battery Mode :
<105% continuous
106-120% for 30 seconds shuts down
121-150% for 10 seconds shuts down
>150% Immediately shuts down.
Buzzer continuously alarms.
Bypass Mode :
<
105
%
continuous
106-120
%
for 250 seconds shuts down
121-130
%
for 125 seconds shuts down
131-135
%
for 50 seconds shuts down
136-145
%
for 20 seconds shuts down
146-148
%
for 5 seconds shuts down
149-157
%
for 2 seconds shuts down
158-176
%
for 1 seconds shuts down
177-187
%
for 0.32 seconds shuts down
>
188
%
for 0.16 seconds shuts down.
Buzzer continuously alarms.
Efficiency
( Full Linear
Load )
Line mode
(Rating 230Vac)
90%
91%
91%
Battery mode
(12Vdc/pcs)
86%
87%
87%
ECO mode
(Rating 230Vac)
97%
97%
97%
MODEL
ITEM
CONTINUITY
PLUS-1K
CONTINUITY
PLUS-2K
CONTINUITY
PLUS-3K
Battery
(Sealed, non-
spillage,
maintenance-
free, lead acid)
Number of batteries
3
6
6
Battery type
12 V/ 7.2 Ah
12 V/ 9 Ah
Rated Battery
Voltage
36 VDC
72 VDC
72 VDC
Backup
time
(Linear
Load)
50%
Load
>11 min
>11 min
>9 min
70%
Load
>8 min
>8 min
> 6 min
100%
Load
> 4 min
> 4 min
> 3 min
Charger
Charge
Current
(Max.)
Standard
2.1A
1.5A
1.5A
Supplem
entary
Charger
(Max.)
(Optional)
3.1A
3.1A
3.1A
Recharge time (to
90%)
4hr
4hr
4hr
Floating Mode
Charging Voltage
40.95Vdc ±1 81.9Vdc±1
81.9Vdc±1
Bluk Mode Charging
Voltage
42.3Vdc±1
84.6Vdc±1
84.6Vdc±1
DC leakage current ≤30 µA with no AC applied and the unit in the
off position
Transfer time
AC to DC
0 ms
Inverter to Bypass
4ms(Typical) 4ms(Typical) / 0ms(Optional)
DC start
Yes
Self
Diagnostics
Upon Power-on, Front Panel Setting &
Software Control, 24 hours routine check
Page
44
to
47
Page
45
to