UPS Maintenance Menus
Use the UPS Maintenance screens to configure and adjust the Alpha FXM to meet your operating needs. To
change parameters, either click the
On/Off
buttons or select an item from a drop down menu.
To execute the changes, click on the
Update Configuration
button.
UPS Maintenance > Unit Configuration
Sets the unit name, input, output and how often the Alpha FXM parameters update.
AC Output Shutdown
When this function is switched
On
, the Alpha FXM inverter is shut off. Neither line nor inverter power is sup- plied
to the load.
DC Output Shutdown
When this function is switched
On
, the LVD configured relay will be de-energized (
Off
).
Applies when ANY programmable dry contact is programmed to be the Low Voltage Disconnect indicator. See
"UPS Maintenance > Relay & Load Shed" on page 41. When the function is switched from
On
to
Off
,
a 10
second delay occurs before the LVD configured relay is energized.
Automatic Frequency Detection
This setting is enabled by default and allows the unit to detect and automatically configure the AC input frequency
(50Hz or 60Hz).
In cases where the AC input frequency can be out of range for long periods, disabling the automatic configuration
prevents the unit from switching back and forth between 50Hz and 60Hz.
Figure 20 — Shown for 230Vac unit, Power set to AVR, Figure 21 — Shown for 230Vac unit, Power set to Quality
Power Quality or AVR
AVR
(Automatic Voltage Regulation) switches on the buck and boost modes.
Quality
switches off the buck and boost modes. The input voltage is the Alpha FXM output voltage.