___________________________________________________________________
Alpha ESS Co., Ltd.
Page 62 of 75
Your Smart Energy
9.3
Powering Off the Product
WARNING
After the inverter and battery pack is powered off, the remaining electricity and heat
may still cause electric shocks and body burns. Therefore, put on protective gloves
and operate the product 5 minutes after the power-off.
Procedure
1. Long press the power button of battery pack for 6 seconds, then switch off the
battery breaker of battery pack.
2. Switch off the battery breaker which is at the left bottom of the inverter.
3. Switch off the PV switch at the left bottom of the inverter.
4. Switch off the PV switch between the PV string and the inverter if there is any.
5. Switch off the AC breaker between the inverter and the load.
6. Switch off the AC breaker between the inverter and the grid.