User Manual
HRU-SlimAIR
If unit shows alert about filter change it is probably time to change filters. Filters replacement is very easy and
you can do it without any additional tools.
NOTE:
Reset the filter counter:
• HRQ-SlimAIR-BUT-LM04:
Reset the dirty filter message by pressing and holding both the AWAY
and AUTO buttons for at least 4 seconds.
• HRQ-SlimAIR-BUT-LM11:
Reset the dirty filter message by pressing and holding both the AWAY
and PARTY buttons for at least 4 seconds.
• Application (option)
: use the “Change filters” button.
6
.10 Heat exchanger cleaning
Heat exchanger ought to be cleansed minimum once a year. The amount of dust layered on the heat exchanger
depends on: frequency of filters change and indoor and outdoor air quality. Heat exchanger can be washed
with warm water with mild detergent (pH from 6 to 8).
To clean heat exchanger:
1. Switch power off
2. Open four clamps placed on side walls and remove cover
3. Unscrew condensate tray (2 torx M4 screws)
4. Turn over heat exchanger lock
5. Remove heat exchanger by pulling strap
6. Place clean or new heat exchanger
7. Screw on heat exchanger lock
8. Close front cover (check if cover is evenly touching the rest of housing)
9. Close four clamps placed on side walls
10. Switch power on
heat exchanger lock
Remove heat exchanger HRU-SlimAIR-250 / HRU-SlimAIR-350