6.2.4 Settings list
NOTE:
The settings of the supply and exhaust fans are not identical, it results from the design of the
air handling unit. If you change the settings of the fans, use the difference (offset) between the
SUPPLY and EXTARCT fans.
Reference factory values can be found in the manual for the air handling unit.
!
No
Description
Range
Default value
1 Standby speed supply
0-40%
Depending on the units
2 Standby speed exhaust
0-40%
Depending on the units
3 Low speed supply
0-80%
Depending on the units
4 Low speed exhaust
0-80%
Depending on the units
5 Medium speed supply
0-100%
Depending on the units
6 Medium speed exhaust
10-100%
Depending on the units
7 High speed supply
0-100%
Depending on the units
8 High speed exhaust
10-100%
Depending on the units
9 Boost speed supply
0-100%
Depending on the units
10 Boost speed exhaust
10-100%
Depending on the units
11 Frost protection pre-heater
setpoint
-20°C to 50°C
-3C
12 Pre-heater function selection
0 – no pre-heater present
1 – ON/OFF Control
2 – Modulating control
1
13 Pre-heater test
0 – normal pre-heater
operation
1 – heater on for 10 seconds
0
14 Bypass manual control
0 – Normal valve operation
1 – Open valve
2 – Close valve
0
15 Daylight saving
1 – None
4 – Europa
4
16 Time-zone offset
Od -840 Do 840 min
Z krokiem co 30 min
0
17 Time edit mode
0 – User
1 – Auto
2 – Bridge
1
18 Time shedule type
1 – 24h(every day the same)
2 – 5-2(Mo-Fr, Sa-Su)
3 – 7 day
2
19 Geothermal heat exchanger
outdoor temperature below
0°C to 10°C
5
20 Geothermal heat exchanger
outdoor temperature above
15°C to 40°C
25
21 Geothermal heat exchanger
valve output
0 - OFF GHE
1 - ON GHE
0