When combining the furnace and evaporator coil
drains together, the A/C condensate drain outlet must
be vented to relieve pressure in order for the furnace
pressure switch to operate properly.
IMPORTANT
(1” min. to 2” Max.above
condensatedrain connection)
Condensate
DrainConnection
Evaporator drain
line required
(Trap at coil is optional)
Figure 48. Furnace with Evaporator Coil Using a
Common Drain
FurnaceCondensate
DrainConnection
From Evaporator Coil
Optional
Field Provided Vent
1” min. 2” max. above
condensate drain.
Figure 49.
Condensate Trap With Optional Overflow
Switch
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
(4” min. to 5” Max.above
condensate drain connection)
5’ max.
PVC Pipe Only
Evaporator
Coil
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
4”min
5”max
Figure 50. Furnace with Evaporator Coil Using a Common Drain