507271-02
Page 6 of 52
Issue 1621
•
Air filters must be replaced upon construction completion.
•
The input rate and temperature rise must be set per the
furnace rating plate.
•
One hundred percent (100%) outdoor air must be provided
for combustion air requirements during construction.
Temporary ducting may supply outdoor air to the furnace.
Do not connect duct directly to the furnace. Size the
temporary duct following the instructions in section for
Combustion, Dilution and Ventilation Air in a confined
space with air from outside.
•
The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction cleanup.
•
All furnace operating conditions (including ignition, input
rate, temperature rise and venting) must be verified
according to these installation instructions.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the
following general recommendations must be considered
when installing one of these furnaces:
•
Place the furnace as close to the center of the air
distribution system as possible. The furnace should
also be located close to the vent termination point.
•
When the furnace is installed in non-direct vent
applications, do not install the furnace where drafts
might blow directly into it. This could cause improper
combustion and unsafe operation.
•
When the furnace is installed in a non-direct vent
applications, do not block the furnace combustion air
opening with clothing, boxes, doors, etc. Air is needed
for proper combustion and safe unit operation.
•
When the furnace is installed in an attic or other
insulated space, keep insulation away from the furnace.
•
When the furnace is installed in an unconditioned space,
consider provisions required to prevent freezing of the
condensate drain system.
NOTE:
The Commonwealth of Massachusetts stipulates
these additional requirements:
•
Gas furnaces shall be installed by a licensed plumber
or fitter only.
•
The gas cock must be “T handle” type.
•
When a furnace is installed in an attic, the passageway
to and service area surrounding the equipment shall be
floored.
Combustion, Dilution & Ventilation Air
If this unit is installed as a Non-Direct Vent Furnace,
follow the guidelines in this section.
NOTE:
In Non-Direct Vent Installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, appliance
vents, chimneys, and fireplaces force additional air that
could be used for combustion out of the house. Unless
outside
air is brought into the house for combustion, negative
pressure (outside pressure is greater than inside pressure)
will build to the point that a down draft can occur in the
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
WARNING
These units should not be installed in areas normally
subject to freezing temperatures.
CAUTION
The State of California has determined that this product
may contain or produce a chemical or chemicals, in very
low doses, which may cause serious illness or death.
It may also cause cancer, birth defects or reproductive
harm.
WARNING
Summary of Contents for 92G1DF-P
Page 17: ...507271 02 Page 17 of 52 Issue 1621 A95DF 95G1DF and A93DF 92G1DF Table 7 ...
Page 18: ...507271 02 Page 18 of 52 Issue 1621 A95DF 95G1DF and A93DF 92G1DF Table 8 ...
Page 31: ...507271 02 Page 31 of 52 Issue 1621 Figure 49 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 36: ...507271 02 Page 36 of 52 Issue 1621 Figure 56 Typical Wiring Diagram For A93DF 92G1DF ...
Page 37: ...507271 02 Page 37 of 52 Issue 1621 Typical Wiring Diagram Figure 57 For A95DF 95G1DF ...
Page 50: ...507271 02 Page 50 of 52 Issue 1621 Start Up Performance Check List ...