Indoor / Outdoor Unit Error Codes
All indoor units provide error code information with either a digital LED display or with Flash codes.
Front Panel
Display window
Figure 25. Indoor Unit Display
Outdoor Unit
LED
Outdoor
Unit LED
Sequence
Indoor Unit
Display
Error Information
Page
Location
1 time
OFF
E0
Indoor unit EEPROM parameter error.
2 times
OFF
E1
Indoor / outdoor units communication error.
3 times
OFF
E2
Zero-crossing signal detection error.
4 times
OFF
E3
The indoor fan speed is operating outside of the normal range.
5 times
OFF
E4
Indoor room temperature sensor T1 is in open circuit or has short
circuited
6 times
OFF
E5
Evaporator coil temperature sensor T2 is in open circuit or has
short circuited.
7 times
OFF
EC
Refrigerant leak detected.
1 times
ON
F0
Overload current protection.
2 times
ON
F1
Outdoor ambient temperature sensor T4 open circuit or short
circuit.
3 times
ON
F2
Condenser coil temperature sensor T3 is in open circuit or has
short circuited.
4 times
ON
F3
Compressor discharge temperature sensor TP open circuit or short
circuit.
5 times
ON
F4
Outdoor unit EEPROM parameter error.
6 times
ON
F5
The outdoor fan speed is operating outside of the normal range.
1 times
FLASH
p0
IPM malfunction or IGBT over-strong current protection.
2 times
FLASH
p1
Over voltage or over low voltage protection.
3 times
FLASH
p2
High temperature protection of IPM module.
5 times
FLASH
p4
Inverter compressor drive error.
Table 14. Indoor and Outdoor Unit Error Codes