Appendix A: Technical Specifications
66
Physical Specifications
Dimensions
Weight
Ventilation
Cabinet (Enclosure) Dimensions
Note
The enclosure size should be determined by considering multiple
factors. This includes the outside ambient temperature, total heat
generated from the installed equipment, sealed or unsealed
enclosure type, enclosure material, paint color, mounting method
(wall, pole, ground, etc.), and sun load. The smaller enclosure size
you choose, the higher risk of overheating the product.
If the product overheats in an enclosure that was built without taking
into account these factors, the warranty of the product might be
voided. Consult Allied Telesis when assistance is needed.
Table 11. Product Dimensions (W x D x H)
IE048-480
70 x 117 x 124 mm
(2.76 x 4.61 x 4.88 in.)
Table 12. Product Weight
IE048-480 with DIN rail bracket
1.2 kg (2.65 lbs)
Table 13. Ventilation Requirements
Minimum Open Space Left and Right Sides
with Adjacent Non-heat Sources
15mm (0.59 in)
Minimum Open Space Left and Right Sides
with Adjacent Heat Sources
50mm (1.97 in)
Minimum Open Space Above and Below
25mm (1.0 in)
Table 14. Minimum Cabinet (Enclosure) Dimensions
Minimum Cabinet Dimensions
(W x H x D)
50.8 x 50.8 x 30.5 cm
(20.0 x 20.0 x 12.0 in)
TBD
Summary of Contents for IE048-480
Page 1: ...613 002833 Rev A IE048 480 Industrial AC DC Power Supply Installation Guide...
Page 6: ...6 I PDF Allied Telesis alliedtelesis com library...
Page 8: ...Contents 8...
Page 10: ...Figures 10...
Page 12: ...Tables 12...
Page 16: ...Preface 16...
Page 42: ...Chapter 2 Beginning the Installation 42...
Page 51: ...IE048 480 Power Supply Installation Guide 51 Figure 12 Installing the Ground Wire...
Page 53: ...IE048 480 Power Supply Installation Guide 53 Figure 13 Installing the AC Power Wires...