Chapter 6: Installing the Power Supplies
112
Installing AT-SBxPWRSYS1 DC System Power Supplies
This section contains the installation procedure for the AT-SBxPWRSYS1
DC System Power Supply. For background information, refer to “Power
Supplies and Power Supply Slots” on page 24.
Warning
The electronic components in the power supply can be damaged by
electro-static discharges (ESD). Follow the procedure in “Protecting
Against Electrostatic Discharge (ESD)” on page 100 to guard
against ESD damage when unpacking and installing the power
supply.
To install the power supply, perform the following procedure:
1. Choose a slot in the chassis for the AT-AT-SBxPWRSYS1 DC System
Power Supply.
System power supplies are installed in slots C and D in the chassis.
Refer to Figure 42 on page 102. If you are installing only one power
supply, you may install it in either slot, but Allied Telesis recommends
slot D because the slot does not come with a blank power supply
panel.
Caution
The AT-SBxPWRSYS1 DC System Power Supply will not work in
slot A or B.
2. If the chassis already has a power supply in slot D, remove the blank
power supply panel from slot C by lifting the blank panel handle and
sliding it out of the slot, as shown in Figure 53 on page 113.
Summary of Contents for AT-SBx8
Page 8: ...Contents 8...
Page 12: ...List of Figures 12...
Page 14: ...List of Tables 14...
Page 18: ...Preface 18...
Page 32: ...Chapter 1 Chassis and Power Supplies 32...
Page 118: ...Chapter 6 Installing the Power Supplies 118...
Page 134: ...Chapter 7 Installing the AT SBx81CFC400 Controller and Ethernet Line Cards 134...
Page 152: ...Chapter 8 Installing the Transceivers and Cabling the Ports 152...
Page 190: ...Chapter 9 Powering On the Chassis 190...
Page 212: ...Chapter 11 Troubleshooting 212...