background image

507867-02

Page 27 of 54

Issue 2128

In both Non–Direct Vent and Direct Vent applications, the 

vent termination is limited by local building codes. In the 

absence of local codes, refer to the current National Fuel 

Gas  Code ANSI  Z223-1/NFPA  54  in  U.S.A.,  and  current 

CSA-B149 Natural Gas and Propane Installation Codes in 

Canada for details.

Position termination according to location given in Figure 

34 or Figure 35. In addition,  position  termination so it is 

free  from  any  obstructions  and  12”  above  the  average 

snow accumulation.

At  vent  termination,  care  must  be  taken  to  maintain 

protective  coatings  over  building  materials  (prolonged 

exposure  to  exhaust  condensate  can  destroy  protective 

coatings). It is recommended that the exhaust outlet not be 

located within 6 feet (1.8 m) of a condensing unit because 

the condensate can damage the painted coating. 

NOTE: 

See  Table  7  for  maximum  allowed  exhaust  pipe 

length  without  insulation  in  unconditioned  space  during 

winter design temperature is below 32° F (0° C). If required, 

exhaust  piping  should  be  insulated  with  1/2”  (13  mm), 

Armaflex or equivalent. In extremely cold climate areas with 

temperature below 20° F (6.7° C) it is recommended that, 

3/4” (19 mm) Armaflex or equivalent be used. Insulation on 

outside runs of exhaust pipe may be painted or wrapped 

to protect insulation from deterioration in accordance with 

the  insulation  manufacturers  recommendation.  Exhaust 

pipe  insulation  may  not  be  necessary  in  some  specific 

applications.

NOTE: 

During  extremely  cold  temperatures,  below 

approximately 20° F (6.7° C), units with long runs of vent 

pipe through unconditioned space, even when insulated, 

may form ice in the exhaust termination that prevents the 

unit from operating properly. Longer run times of at least 5 

minutes will alleviate most icing problems. Also, a heating 

cable may be installed on exhaust piping and termination 

to  prevent  freeze-ups.  Heating  cable  installation  kits  are 

available. See unit specification sheets for part numbers.

Do  not  use  screens  or  perforated  metal  in  exhaust 

terminations. Doing so will cause freeze-ups and may 

block the terminations.

 IMPORTANT

For Canadian Installations Only:

In  accordance  to  CSA  International  B149  installation 

codes,  the  minimum  allowed  distance  between  the 

combustion  air  intake  inlet  and  the  exhaust  outlet  of 

other appliances shall not be less than 12 inches (305 

mm).

 IMPORTANT

Details of Intake and Exhaust Piping 

Terminations for Direct Vent Installations

NOTE: 

In Direct Vent installations, combustion air is taken 

from outdoors and flue gases are discharged to outdoors.

NOTE: 

Flue gas may be slightly acidic and may adversely 

affect  some  building  materials.  If  any  vent  termination 

is used and the flue gases may impinge on the building 

material, a corrosion-resistant shield (minimum 24 inches 

square)  must  be  used  to  protect  the  wall  surface.  If  the 

optional  tee  is  used,  the  protective  shield  is  required. 

The  shield  should  be  constructed  using  wood,  plastic, 

sheet  metal  or  other  suitable  material. All  seams,  joints, 

cracks, etc. in the affected area should be sealed using an 

appropriate sealant. See Figure 44. 

Intake and exhaust pipes may be routed either horizontally 

through and outside wall or vertically through the roof. In 

attic or closet installations, vertical termination through the 

roof is preferred. Figure 36 through Figure 43 show typical 

terminations.

1.  Intake and exhaust terminations are not required to be 

in the same pressure zone. You may exit the intake on 

one side of the structure and the exhaust on another 

side (Figure 37). You may exit the exhaust out the roof 

and the intake out the side of the structure (Figure 38).

2.  Intake and exhaust pipes should be placed as close 

together  as  possible  at  termination  end  (refer  to 

illustrations).  Minimum  separation  is  3”  (76  mm) 

on  roof  terminations  and  6”  (152  mm)  on  sidewall 

terminations.

3.  On roof terminations, the intake piping should terminate 

straight down using two 90° elbows (see Figure 36).

4.  Exhaust  piping  must  terminate  straight  out  or  up  as 

shown.  A  reducer  may  be  required  on  the  exhaust 

piping  at  the  point  where  it  exits  the  structure  to 

improve the velocity of exhaust away from the intake 

piping. See Table 8.

Table 8. Exhaust Pipe Termination Size Reduction

Capacity

Exhaust Pipe Size

Termination Pipe Size

*

030, 

045 

and 070

1-1/2” (38 mm),

 

 2” (51 mm), 

 

2-1/2” (64 mm), 

 

3” (76 mm)

1-1/2” (38 mm)

*090

2” (51 mm), 

 

2-1/2” (64 mm), 

 

3” (76 mm)

2” (51 mm)

110

-030, -045, -070, and -090 units with the flush mount 

termination must use the 1-1/2” accelerator supplied with the 

kit.

NOTE: 

Care  must  be  taken  to  avoid  recirculation  of 

exhaust back into intake pipe.

Summary of Contents for 030-B12

Page 1: ...amage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical eq...

Page 2: ...Issue 2128 Unit Dimensions FRONT VIEW SIDE VIEW Capacity A B C D in mm in mm in mm in mm 030 B12 045 B12 070 B12 17 1 2 446 16 3 8 416 16 406 1 5 8 194 090 C12 090 C16 110 C16 110 C20 21 533 19 7 8 50...

Page 3: ...lve Combustion Air Inducer Blower Access Door Combustion Air Pressure Prove Switch Cold End Header Box Control Box includes integrated ignition control transformer and interlock switch Blower Assembly...

Page 4: ...Snap bushing 1 Snap Plug 1 Wire tie 1 Condensate trap 1 Condensate trap cap 1 Condensate trap clamp 1 2 diameter debris screen 1 3 4 Threaded street elbow Check equipment for shipping damage If you fi...

Page 5: ...dards NOTE Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate Failure to do so may cause erratic limit operation and premature heat exchanger failur...

Page 6: ...ALL OF THE FOLLOWING CRITERIA ARE MET a Furnace must be in its final location The vent system must be permanently installed per these installation instructions b Furnace must be installed as a two pi...

Page 7: ...inated atmosphere Meet all combustion and ventilation air requirements as well as all local codes CAUTION In the absence of local codes concerning air for combustion and ventilation use the guidelines...

Page 8: ...a minimum free area of 1 square inch per 4 000 Btu 645 mm per 59 kW per hour of total input rating of all equipment in the enclosure see Figure 6 and Figure 7 It is also permissible to bring in air fo...

Page 9: ...let Air to Outside Ventilation Louvers Inlet Air Minimum 12 in 305mm above Attic Floor Roof Terminated Exhaust Pipe Furnace Intake Debris Screen Provided See Maximum Vent Lengths table NOTE The inlet...

Page 10: ...late Also consider gas supply connections electrical supply vent connection and installation and service clearances 24 inches 610 mm at unit front The unit must be level Do not connect the return air...

Page 11: ...th optional RAB Return Air Base Bottom return air Return air from both sides Bottom and one side return air FRONT VIEW SIDE VIEW 1 Unit side return air Opening 3 1 4 83 1 23 584 Overall Maximum 584 23...

Page 12: ...Left End Air Flow Air Flow Left Hand Discharge Bottom floor Right End Left End Air Flow Air Flow Top Plenum 1 in 25 mm Front 0 Back 0 Sides 0 Vent 0 Floor 0 Front clearance in alcove installation mus...

Page 13: ...lters This unit is not equipped with a filter or rack Afield provided filter is required for the unit to operate properly Table 1 list recommended filter sizes A filter must be in place whenever the f...

Page 14: ...vent pipe hangers Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket Canad...

Page 15: ...et surface and end of pipe are wet with cement forcefully insert end of pipe into socket until it bottoms out Turn PVC pipe 1 4 turn Capacity VENT PIPE DIA in STANDARD CONCENTRIC Outdoor Exhaust Accel...

Page 16: ...blockage restriction leakage corrosion or other deficiencies which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remain...

Page 17: ...urnace NOTE In non Direct Vent installations combustion air is taken from indoors and flue gases are discharged outdoors In Direct Vent installations combustion air is taken from outdoors and flue gas...

Page 18: ...ck the terminations IMPORTANT Use Figure 24 to correctly size vent pipe diameter 030 045 070 090 110 Standard or Concentric See Table 3 Intake or Exhaust 1 1 2 2 2 1 2 or 3 Furnace capacity 1 Which te...

Page 19: ...26 n a 75 60 28 n a 97 97 78 78 9 36 21 70 55 23 92 92 73 73 10 31 16 65 50 18 87 87 68 68 Concentric Termination Elevation 0 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Cap...

Page 20: ...65 50 18 82 82 63 63 8 31 16 60 45 13 77 77 58 58 9 26 11 55 40 8 72 72 53 53 NOTE Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total...

Page 21: ...n horizontal runs of exhaust pipe When transitioning up in pipe size use the shortest length of 2 PVC pipe possible When transitioning down in pipe size use at least 1 foot of 2 PVC pipe NOTE Exhaust...

Page 22: ...and guidelines listed in Combustion Dilution and Ventilation Air section must be followed Follow the next two steps when installing the unit in Direct Vent applications where combustion air is taken...

Page 23: ...take air inlet will not be obstructed by loose insulation or other items that may clog the debris screen 2 If intake air is drawn from a ventilated attic Figure 31 or ventilated crawlspace Figure 32 t...

Page 24: ...N A 3 in N A N A 9 9 18 18 35 35 47 47 20 to 1 7 to 17 1 1 2 in N A N A 15 N A 20 N A N A N A N A N A 2 in N A N A 9 8 18 16 32 29 30 30 2 1 2 in N A N A 5 N A 13 N A 24 N A 34 N A 3 in N A N A N A N...

Page 25: ...arance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for...

Page 26: ...s 152mm for appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btu...

Page 27: ...tallation codes the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches 305 mm IMPORTANT Details of Intake and...

Page 28: ...44 6 On field supplied terminations a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8 and a minimum distance of 6 with a terminatio...

Page 29: ...045 and 070 models EXHAUST VENT Figure 41 Direct Vent Concentric Wall Termination 71M80 69M29 or 60L46 US 44W92 or 44W93 Canada Figure 42 STRAIGHT CUT OR ANGLE CUT IN DIRECTION OF ROOF SLOPE EXHAUST V...

Page 30: ...d be connected to the 2 or 3 PVC flue pipe as shown in the illustration Do not use an accelerator in applications that include an exhaust termination tee The accelerator is not required 2 As required...

Page 31: ...CUMULATION SIZE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Figure 46 Non Direct Vent Field Supplied Wall Termination SIZE TERMINATION PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE FIELD PRO...

Page 32: ...ermination Drain Trap assembled Figure 49 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure...

Page 33: ...n tape or appropriate pipe dope 3 Install the cap over the clean out opening at the base of the trap Secure with clamp See Figure 58 4 Install drain trap using appropriate PVC fittings glue all joints...

Page 34: ...iping from furnace must slope down a minimum of 1 4 per ft toward trap Figure 55 Evaporator Coil Using a Separate Drain Figure 56 Evaporator Coil Using a Common Drain Piping from furnace must slope do...

Page 35: ...507867 02 Page 35 of 54 Issue 2128 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...

Page 36: ...ide of unit See Figure 61 and Figure 62 4 Piping should be sloped 1 4 per 15 feet 6 mm per 5 6 m upward toward the gas meter from the furnace The piping must be supported at proper intervals every 8 t...

Page 37: ...ted WARNING Figure 61 Gas Piping Upflow Applications NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIELD PROVIDED AND INSTALLED GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Upflow...

Page 38: ...16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 8 2 067 52 50...

Page 39: ...wer for service Complete the wiring connections to the equipment Use the provided unit wiring diagram and the field wiring diagram shown in Figure 66 Use 18 gauge wire or larger that is suitable for C...

Page 40: ...the heating speed 3 When there is a cooling demand the indoor blower will run on the cooling speed Generator Use Voltage Requirements The furnace requires 120 volts 10 Range 108 volts to 132 volts Th...

Page 41: ...507867 02 Page 41 of 54 Issue 2128 Figure 67 Typical Wiring Diagram...

Page 42: ...ARNING Danger of explosion Can cause injury or product or property damage Should the gas supply fail to shut off or if overheating occurs shut off the gas valve to the furnace before shutting off the...

Page 43: ...r to the unit 11 Set the thermostat to desired setting NOTE When unit is initially started steps 1 through 11 may need to be repeated to purge air from gas line 12 If the appliance will not operate fo...

Page 44: ...bilize observe the flame Flame should be stable and should not lift from burner Natural gas should burn blue 4 After allowing unit to stabilize for 5 minutes record manifold pressure and compare to va...

Page 45: ...s installation of a gas valve regulator spring which is provided with the gas conversion Kit LP Kits include low line pressure switch Table 13 Burner Orifice Conversion Kits at Varying Altitudes Capac...

Page 46: ...d and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dryers and any appliances not connected to the venting system Turn on any exhaust fans such as range hoods and bathroom e...

Page 47: ...ess panel in place Motor Nameplate__________Actual__________ Blower Speeds Follow the steps below to change the blower speeds 1 Turn off electrical power to furnace 2 Remove blower access panel 3 Disc...

Page 48: ...90 348 1270 271 1135 199 885 109 735 71 0 20 1355 349 1230 280 1100 207 850 119 680 81 0 30 1330 368 1205 291 1060 220 795 126 625 84 0 40 1295 378 1180 298 1025 226 755 134 570 91 0 50 1265 386 1140...

Page 49: ...06 1275 173 1160 135 0 20 1655 392 1460 273 1315 219 1230 185 1110 142 0 30 1615 408 1410 282 1290 225 1195 192 1065 151 0 40 1595 416 1365 295 1245 236 1155 203 1010 160 0 50 1560 429 1335 308 1200 2...

Page 50: ...33 1880 441 1715 353 1605 288 1435 210 2135 614 1885 421 1705 342 1595 280 1415 207 0 20 2085 648 1830 455 1665 362 1560 298 1360 220 2085 628 1830 437 1670 351 1545 293 1370 218 0 30 2040 663 1795 46...

Page 51: ...intake pipes and all connections for tightness and to make sure there is no blockage NOTE After any heavy snow ice or frozen fog event the furnace vent pipes may become restricted Always check the ven...

Page 52: ...ating correctly 19 Replace heating compartment access panel Table 17 Control Diagnostic Codes Integrated Control LED Codes Red LED Flash Code2 Diagnostic Codes Status of Furnace LED Off No power to co...

Page 53: ...s Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furna...

Page 54: ...height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...

Reviews: