![Alliance Laundry Systems SE3930 Service Manual Download Page 25](http://html1.mh-extra.com/html/alliance-laundry-systems/se3930/se3930_service-manual_2901326025.webp)
53273
25
Section 4 Service Procedures
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the dryer(s) before servicing.
• Close gas shut-off valve to gas dryer(s) before servicing.
• Never start the dryer(s) with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the dryer is properly grounded.
W001R1
WARNING
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
b. Burner Tube and Igniter – Refer to
NOTE: Burner tube and igniter can be removed
without removing gas valve and bracket.
(1) Remove screw from right side of burner
housing holding burner tube in place. Refer
to Figure 12.
(2) Gently move burner tube toward rear of
dryer to disengage tab from slot on left side
of burner housing. Refer to Figure 12.
(3) Carefully rotate burner tube and igniter
counterclockwise so tab is at 8 o’clock
position.
(4) Move air shutter end of burner tube slightly
to right and CAREFULLY remove burner
tube and igniter assembly.
IMPORTANT: Use care in removal so as not to
damage or break igniter as it is very fragile.
IMPORTANT: Handle igniter by grasping the
white ceramic portions only. DO NOT handle silicon
carbide portion of igniter with hands or allow any
oil, grease or other foreign material to contaminate
it. Oil, grease and other impurities or hairline
cracks will cause the igniter to burn out.
Figure 11
DRY1212S
THROUGH SERIAL NO. S840L627
Access
Door
Lock
Support
Access
Door
DRY951S
STARTING SERIAL NO. S840L628
Support
Access
Door
Washer
Phillips
Head
Screw
To Test Gas Valve Coil Assembly
1. Disconnect electrical service.
2. Disconnect valve wire harness from dryer
harness at molex plug.
3. Set test meter to read ohms and put meter probes
on BLUE and BLACK wire terminals on valve
harness side of molex plug.
4. Meter should read approximately 100 ohms with
the igniter (glow bar) in the circuit. If reading
goes to approximately 400 ohms, replace the
igniter.
5. If meter registers other than approximately 10
ohms as explained in step 4, one of the coils has
failed. Replace the coil assembly.