116
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Chapter 4
Programming
Table 24 - 150-SM4 Parameters
Parameter
Min/Max Values
Default Value
Access
Units
Number
(1)
Name
X.1
Module Status
Bit 0 = Module Ready/Disabled
Bit 1 = Input 1 Status
Bit 2 = Input 2 Status
Bit 3 = Input 3 Status
Bit 4 = Input 4 Status
Bit 5 = Aux 1 Status
Bit 6 = Aux 2 Status
Bit 7 = Aux 3 Status
—
R
0 = Disabled OFF
1 = Enabled ON
X.2
Input 1
Disable
Start
Coast
Stop Option
Start/Coast
Start/Stop
Dual Ramp
OL Select
Fault
Fault NC
Clear Fault
Emerg Run
Motor Heater
Disable
R/W
NA
X.3
Input 2
X.4
Input 3
X.5
Input 4
X.6
Aux 1 Config
[Normal]
UTS (Up-to-Speed)
Fault
Alarm
Ext Bypass
Ext Brake
DeviceLogix
Aux Control
(2)
Network 1
Network 2
Network 3
Network 4
Fan Control
Normal
R/W
NA
X.7
Aux 1 Invert
Disable
Enable
Disable
R/W
X.8
Aux 1 On Delay
0.0…10.0
0.0
R/W
seconds
X.9
Aux 1 Off Delay
0.0…10.0
0.0
R/W
seconds
X.10
Aux 2 Config
Normal
UTS (Up-to-Speed)
Fault
Alarm
Ext Bypass
Ext Brake
DeviceLogix
Aux Control
(2)
Network 1
Network 2
Network 3
Network 4
Fan Control
Normal
R/W
NA
X.11
Aux 2 Invert
Disable
Enable
Disable
R/W
NA
X.12
Aux 2 On Delay
0.0…10.0
0.0
R/W
seconds
X.13
Aux 2 Off Delay
0.0…10.0
0.0
R/W
seconds
X.14
Aux 3 Config
[Normal]
UTS (Up-to-Speed)
Fault
Alarm
Ext Bypass
Ext Brake
DeviceLogix
Aux Control
(2)
Network 1
Network 2
Network 3
Network 4
Fan Control
Normal
R/W
NA
X.15
Aux 3 Invert
Disable
Enable
Disable
R/W
NA
X.16
Aux 3 On Delay
0.0…10.0
0.0
R/W
seconds
X.17
Aux 3 Off Delay
0.0…10.0
0.0
R/W
seconds
X.18
Parameter Mgmt
Ready
Factory Default
Ready
R/W
NA
(1) "X" indicates the port number (07, 08, or 09) the 150-SM4 is connected to the SMC-50 control module. This port number is displayed on the HIM screen below the Allen-Bradley brand logo.
(2) An auxiliary output configured for Aux Control using the AuxX Config parameter is under control of its associated bit form the AuxControl, Parameter 180.
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......