Publication 1747-6.5.5 - August 2000
5-12
Communicating with DeviceNet from Another Network
Communicating with
DeviceNet via a DH+
Network
Before performing this example the DH+ network must be configured
and running. This example uses a SLC 5/04 processor. The SLC 5/04
processor lets you operate DH
+
communication protocol by means of
DH
+
communication channel 1.
Configuring the DeviceNet Pass-Through Driver
Before you can communicate with the 1747-SDN module via a DH+
network, you must first configure the DeviceNet pass-through driver
(1747-SDNPT) with a DH+ port using RSLinx, version 2.10 or higher.
Use the following procedure:
1.
Start
RSLinx
.
2.
From the
Communications
menu, select
Configure Drivers
.
The
Configure Drivers
window will appear.
3.
Select
DeviceNet Drivers
from the
Available Driver Types
pull-down list and click on
Add/New
.
Summary of Contents for SLC 500 DeviceNet
Page 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Page 4: ......
Page 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Page 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Page 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Page 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Page 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Page 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Page 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Page 137: ......