
1
Publication 1747-6.5.5 - August 2000
Appendix
B
Configuring the M0/M1 Files Using
RSLogix 500
RSLogix 500
I/O Configuration
To enable pass-through access using a SLC 500 processor, you must
configure the M0 and M1 files associated with the 1747-SDN module
at a minimum length of 361 words.
Use the following procedure to configure the 1747-SDN’s M0 and M1
files using RSLogix 500 software.
1.
Run
RSLogix 500
and go offline to the SLC 500 processor.
2.
Under the
Controller
folder in the Project window, double-click
on
IO Configuration
.
The
I/O Configuration
window will open.
3.
Click on the
Read I/O Config
. button to upload the I/O
configuration from the processor.
Summary of Contents for SLC 500 DeviceNet
Page 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Page 4: ......
Page 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Page 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Page 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Page 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Page 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Page 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Page 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Page 137: ......