Rockwell Automation Publication 520-UM002B-EN-E - December 2017
131
Troubleshooting
Chapter 7
Logix Designer Axis Properties - Actions Category
Drive Behavior, FLT Sxx Fault Codes
Exception Fault Code
Exception Text
Induction
Motor
Fault Action
Best Available Stopping
Action (applies to major
faults)
Ignore
Alarm
Minor
Fault
Major
Fault
FLT S03 – MTR OVERSPEED FL
Motor Overspeed Factory Limit Fault
X
X
Disable and Coast
FLT S04 – MTR OVERSPEED UL
Motor Overspeed User Limit Fault
X
X
X
X
X
Disable and Coast
FLT S07 – MTR OVERLOAD FL
Motor Thermal Overload Factory Limit Fault
X
X
Disable and Coast
FLT S08 – MTR OVERLOAD UL
Motor Thermal OverLoad User Limit Fault
X
X
X
X
X
Disable and Coast
FLT S10 – INV OVERCURRENT
Inverter Overcurrent Fault
X
X
Disable and Coast
FLT S11 – INV OVERTEMP FL
Inverter Overtemperature Factory Limit Fault
X
X
Disable and Coast
FLT S13 – INV OVERLOAD FL
Inverter Thermal Overload Factory Limit Fault
X
X
Disable and Coast
FLT S16 – GROUND CURRENT
Ground Current Factory Limit Fault
X
X
Disable and Coast
FLT S23 – AC PHASE LOSS
AC Single Phase Loss Fault
X
X
X
X
X
Disable and Coast
FLT S25 – PRECHARGE FAILURE
Pre-charge Failure Fault
X
X
Disable and Coast
FLT S29 – BUS OVERLOAD FL
Bus Regulator Thermal OverLoad Factory Limit Fault
X
X
Disable and Coast
FLT S34 – BUS UNDERVOLT UL
Bus Undervoltage User Limit Fault
X
X
X
X
X
Disable and Coast
FLT S35 – BUS OVERVOLT FL
Bus Overvoltage Factory Limit Fault
X
X
Disable and Coast
FLT S37 – BUS POWER LOSS
Bus Power Loss
X
X
X
X
X
Disable and Coast
FLT S41 – FDBK SIGNAL NOISE FL Feedback Signal Noise Fault
X
X
X
X
X
Disable and Coast
FLT S45 – MTR FDBK COMM FL
Motor Feedback Data Loss Factory Limit Fault
X
X
X
X
X
Disable and Coast
FLT S50 – HARDWARE
OVERTRAVEL POSITIVE
Hardware Overtravel Positive
X
X
X
X
X
Current Decel and Disable
FLT S51 – HARDWARE
OVERTRAVEL NEGATIVE
Hardware Overtravel Negative
X
X
X
X
X
Current Decel and Disable
FLT S54 – POSN ERROR
Excessive Position Error Fault
X
X
X
X
X
Disable and Coast
FLT S55 – VEL ERROR
Excessive Velocity Error Fault
X
X
X
X
X
Disable and Coast
FLT S56 – OVERTORQUE LIMIT
Overtorque Limit Fault
X
X
X
X
X
Disable and Coast
FLT S57 – UNDERTORQUE LIMIT
Undertorque Limit Fault
X
X
X
X
X
Disable and Coast
FLT S61 – ENABLE INPUT
DEACTIVATED
Enable Input Deactivated
X
X
X
X
X
Disable and Coast
Summary of Contents for PowerFlex 527
Page 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Page 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Page 175: ......