Rockwell Automation Publication 20P-TG001C-EN-P - February 2018
85
Part Replacement Procedures
Chapter 3
• For Non-Regenerative drives, remove the screws and washers that
secure the U and V Phase terminal bus bars to the corresponding
SCR modules.
10. While lifting the terminal bus bars out of the drive, slide the AC current
transducers off the bus bars.
Install the AC Current Transducers
Install the AC current transducers in reverse order of removal.
For AC current transducers that must be wound with wire leads:
• Wind the wire leads around the new AC current transducers:
• Wind the wires the same number of times as the wires on the old AC
current transducers
• Wind the wires in the same position as the wires on the old AC
current transducers
• Crimp the connection lugs onto the wire leads before they are secured to
the power traces board.
9
Tightening torque:
2.5…4 N•m (22…35.4 lb•in)
Wrap wire around AC
Current Transducer
Crimp connection lug
onto wire ends