28
Rockwell Automation Publication 20P-TG001C-EN-P - February 2018
Chapter 2
Component Test Procedures
Power Component Test
Procedures
Follow the applicable procedure for the affected power components.
Check the Armature SCR Modules
The frame A PowerFlex DC drive armature supply consists of three (non-
regenerative drives) or six (regenerative drives) SCR modules that are mounted
on the main heat sink. One of the following can indicate a malfunction of any
of these modules:
• An Overcurrent fault (F13)
• Blown or tripped incoming protection devices
• Erratic motor operation
If an armature bridge component malfunction is suspected, follow these steps.
1. Read the General Safety Precautions on page
2. Remove power from the drive (see page
3. Verify that contactor power (if used) is removed.
4. Verify that power to an external field supply (if used) is removed.
5. Check the anode to cathode junction of each SCR. With a digital
multimeter set to Ohms, measure the resistance across the SCRs (lead
orientation is not critical).
• For regenerative drives, see
and
on
page
• For non-regenerative drives, see
on page
and
page
If a low resistance is detected, determine which SCR module is damaged
based on
and replace that module (see SCR Module
Replacement on page