Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
21
Installing the HIM
Chapter 2
3.
Insert the supplied 3 m/9.8 ft. long 1202-C30 HIM cable into the mating
socket on the back of the HIM.
4.
Install the supplied O-ring into the cable routing hole on the panel to
protect the cable.
5.
Route the HIM cable through the cable routing hole on the panel.
6.
Align the six threaded studs of the HIM with the panel clearance holes,
and place the HIM against the panel.
7.
Tighten the nuts onto the six threaded studs of the HIM extending behind
the panel.
Recommended torque is 0.68 N•m (6.0 lb•in).
8.
Route the HIM cable to the drive.
9.
Connect the HIM cable to the DPI Port 2 on the drive as shown on
for a PowerFlex 750-Series drive or a PowerFlex 7-Class drive.
Removing the HIM
Remove the HIM from the drive HIM bezel or the remote-mount HIM bezel in
reverse order of how it was installed.
ATTENTION:
Risk of injury or equipment damage exists. If the HIM cable or
remote-mount HIM bezel cable is disconnected from DPI Port 2 on the drive, the
drive may fault. Determine how the drive will respond before disconnecting the
cable.
IMPORTANT
The Host drive can remain powered when removing the HIM. However, a fault
will occur if the HIM is not the last controlling device and does not have Manual
control of the Host drive. To avoid a fault in this case, access the HIM Control
screen (shown on
), press the
key, and then remove the HIM
from the Host drive.
Summary of Contents for PowerFlex 20-HIM-A6
Page 4: ...4 Rockwell Automation Publication 20HIM UM001E EN P May 2017 Summary of Changes Notes ...
Page 8: ...8 Rockwell Automation Publication 20HIM UM001E EN P May 2017 Table of Contents Notes ...
Page 66: ...66 Rockwell Automation Publication 20HIM UM001E EN P May 2017 Chapter 4 Using the HIM Notes ...
Page 70: ...70 Rockwell Automation Publication 20HIM UM001E EN P May 2017 Appendix B HIM Parameters Notes ...
Page 73: ......