Using I/O Messaging
5-5
32-Bit Parameters using 16-Bit Datalinks
To read (and/or write) a 32-bit parameter using 16-bit Datalinks,
typically both Datalinks (A,B,C,D) are set to the 32-bit parameter. For
example, to read
Parameter 09 - [Elapsed MWh]
, both Datalink A1
and A2 are set to “9.” Datalink A1 will contain the least significant word
(LSW) and Datalink A2 the most significant word (MSW). In this
example, the parameter 9 value of 5.8MWh is read as a “58” in Datalink
A1.
Regardless of the Datalink combination, x1 will always contain the LSW
and x2 will always contain the MSW. In the following examples
Parameter 242 - [Power Up Marker]
contains a value of 88.4541
hours.
32-bit data is stored in binary as follows:
Example:
Parameter 242 - [Power Up Marker]
= 88.4541 hours
MSW = 13
decimal
= 1101
binary
= 2
16
+ 2
18
+ 2
19
= 851968
LSW = 32573
32573 = 884541
Datalink
Most/Least Significant Word
Parameter Data (decimal)
A1
LSW
9
58
A2
MSW
9
0
Datalink
Most/Least Significant Word
Parameter Data (decimal)
A1
LSW
242
32573
A2
- Not Used -
0
0
Datalink
Most/Least Significant Word
Parameter Data (decimal)
A1
- Not Used -
0
0
A2
MSW
242
13
Datalink
Most/Least Significant Word
Parameter Data (decimal)
A2
MSW
242
13
B1
LSW
242
32573
MSW
2
31
through 2
16
LSW
2
15
through 2
0
Summary of Contents for PowerFlex 20-COMM-D
Page 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Page 6: ...iv Table of Contents Notes...
Page 72: ...6 14 Using Explicit Messaging Notes...
Page 90: ...B 8 Adapter Parameters Notes...
Page 122: ...C 32 DeviceNet Objects Notes...
Page 132: ...E 8 Master Slave I O Configuration Notes...
Page 148: ......