Configuring the Adapter
3-7
If the adapter Data Rate switch is set to “PGM,” the value of
Parameter
03 - [DN Addr Cfg]
determines the node address. We recommend that
you do not use node address 63 because all new devices use it as the
default address. Address 63 is also used for Automatic Device Recovery
(ADR).
1.
Set the value of
Parameter 03 - [DN Addr Cfg]
to a unique node
address.
Figure 3.5 DeviceNet Node Address Screen on an LCD HIM
2.
Reset the adapter. Refer to the
chapter.
If the adapter Data Rate switch is set to “PGM,” the value of
Parameter
05 - [DN Rate Cfg]
determines the DeviceNet data rate. The Autobaud
setting will detect the data rate used on the network if another device is
setting the data rate. Your application may require a different setting.
1.
Set the value of
Parameter 05 - [DN Rate Cfg]
to the data rate at
which your network is operating.
Figure 3.6 DeviceNet Data Rate Screen on an LCD HIM
2.
Reset the adapter. Refer to the
chapter.
Setting the Node Address
Port 5 Device
20-COMM-D
Parameter #: 3
DN Addr Cfg
63
0 <> 63
Default = 63
TIP:
If you are using RSNetWorx for DeviceNet, select
Network >
Single Browse Path
to see the new address; then delete the old address.
Setting the Data Rate
Value Baud Rate
0
125 kbps
1
250 kbps
2
500 kbps
3
Autobaud (Default)
Port 5 Device
20-COMM-D
Parameter #: 5
DN Rate Cfg
3
Autobaud
Summary of Contents for PowerFlex 20-COMM-D