258
Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Chapter 5
I/O Wiring
Analog Current Input
Unipolar Speed Reference
0-20 mA Input
22-Series I/O Module TB1
•
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
•
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port X (22-Series I/O Module): P50 [Anlg In0 Value]
•
Adjust Scaling
Port X (22-Series I/O Module): P51 [Anlg In0 Hi] = 20 mA
Port X (22-Series I/O Module): P52 [Anlg In0 Lo] = 0 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
•
View Results
Port X (22-Series I/O Module): P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
HW Input PTC
Standard = DIN 44082
PTC Nominal = 1.8 k Ohm
PTC Trip = 3.1 k Ohm
PTC Reset = 2.2 k Ohm
Short Circuit Trip = 300 Ohm
22-Series I/O Module TB1
•
Configuration
Port X (22-Series I/O Module): P40 [PTC Cfg] = 0 “Ignore,” 1 “Alarm,” 2 “Flt Minor,”
3 “Flt CoastStop,” 4 “Flt RampStop,” or 5 “Flt CL Stop”
•
View Results
Port X (22-Series I/O Module): P41 [PTC Sts]
Port X (22-Series I/O Module): P42 [PTC Raw Value]
Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar
22-Series I/O Module TB1
•
Configuration
Port X (22-Series I/O Module): P70 [Anlg Out Type], bit 0 = 0
•
Set Selection
Port X (22-Series I/O Module): P75 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]
•
Adjust Scaling
Port X (22-Series I/O Module): P78 [Anlg Out0 DataHi] = 60 Hz
Port X (22-Series I/O Module): P79 [Anlg Out0 DataLo] = 0 Hz
Port X (22-Series I/O Module): P80 [Anlg Out0 Hi] =10V/20 mA
Port X (22-Series I/O Module): P81 [Anlg Out0 Lo] = 0V/0 mA
•
View Results
Port X (22-Series I/O Module): P77 [Anlg Out0 Data]
Port X (22-Series I/O Module): P82 [Anlg Out0 Val]
2-Wire Control Non-
Reversing
24V DC internal supply
22-Series I/O Module TB1
•
Set Direction Mode
Port 0: P308 [Direction Mode] = 2 “Rev Disable”
•
Set Selection
Port 0: P163 [DI Run] = Port X (22-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0
•
View Results
Port X (22-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
2-Wire Control Reversing
External 24 volt supply
20-750-2262C-2R
20-750-2263C-1R2T
22-Series I/O Module TB1
•
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
•
Set Selection
Port 0: P164 [DI Run Forward] = Port X (22-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port X (22-Series I/O Module): P1 [Dig In Sts], bit 1 = Input 1
•
View Results
Port X (22-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
22-Series I/O Module TB1 Wiring Examples (Continued)
Input/Output
Connection Example
Required Parameter Changes
Ai0–
Ai0+
Common
+
Ai0
Ai1
1.8k
PTC
Ptc–
Ptc+
ATTENTION:
To avoid an electric shock hazard, the connection of the motor
temperature sensor requires double or reinforced insulation between motor live
parts and the PTC.
Ao0–
Ao0+
+
–
24VC
+24V
Di C
Di 0
Stop-Run
Di C
Di 0
Di 1
+24V
Common
Run Fwd
Run Rev
Summary of Contents for PowerFlex 20-750-20COMM
Page 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Page 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Page 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Page 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...
Page 301: ......