Publication 1734-UM005B-EN-P - June 2001
Configuring the POINT I/O System
3-11
If you select “Hold Last State,” the module outputs are frozen in their
current state. If you select “Fault Value,” you need to define the Fault
Value parameter. Possible settings are: digital modules - ON/OFF;
analog modules - any value within a predefined range.
Configure Idle Action Value for your Output Modules
When the adapter receives a clear command from the master, the
adapter puts all connected I/O modules into their Idle state.
Enter the value you wish to use.
(Click on “OK” to continue.)
Module parameters
Select the “Fault Value” parameter.
(Click on “OK” to continue.)
Module parameters
Select the “Idle Value”
parameter.
(Click on “OK” to continue.)
Select the desired state.
Possible settings are “Idle
Value,” and “Hold Last State
(HLS).
(Click on “OK” to continue.)