Publication 1734-UM003A-EN-P - August 2000
Very High Speed Counter Module Input and Output Data
3-9
Scalar (Configuration Word 7)
This byte scales the Z signal in the
period/rate [5]
and
continuous/rate
[6]
configurations. If the filter is applied, then the filtered Z is scaled.
Only one bit of the scalar should be set. Selecting a scalar will cause
accumulated counts to be adjusted accordingly (i.e. selecting a scalar
of 128 will increase the accumulated count by 128 after 128 Z pulses
have been received
).
It is highly recommended that anytime Z is
scaled (divide by 2, 4, 8, etc), the Z input should be filtered,
otherwise, noise could cause erroneous frequency readings.
Scalar Selection
Output 0-1 Ties (Configuration Words 8 and 9)
The bits in these two bytes connect the specified output to the
appropriate compare window. There are 4 windows associated with
the counter. Each output may be connected to any number of
windows, from 1 to all 4. The bits are defined as follows:
T0 -
Tie Output to 1
st
Compare Window (also the PWM signal in
PWM [3]
configuration)
T1 -
Tie Output to 2
nd
Compare Window
T2 -
Tie Output to 3
rd
Compare Window
T3 -
Tie Output to 4
th
Compare Window
07
06
05
04
03
02
01
00
Scalar
1
0
0
0
0
0
0
0
1
Z - F
min
= 0.149Hz
0
0
0
0
0
0
1
0
Z/2 - F
min
= 0.298Hz
0
0
0
0
0
1
0
0
Z/4 - F
min
= 0.596Hz
0
0
0
0
1
0
0
0
Z/8 - F
min
= 1.192Hz
0
0
0
1
0
0
0
0
Z/16 - F
min
= 2.384Hz
0
0
1
0
0
0
0
0
Z/32 - F
min
= 4.768Hz
0
1
0
0
0
0
0
0
Z/64 - F
min
= 9.537Hz
1
0
0
0
0
0
0
0
Z/128 - F
min
= 19.073Hz
1 Where F
min
indicates the frequency at which the zero frequency detect is asserted
due to counter overflow.