Allen-Bradley POINT I/O 1734-IE2C Installation Instructions Manual Download Page 1

Installation Instructions

POINT I/O 2 Current and 2 Voltage Input 
Analog Modules

Catalog numbers 1734-IE2C,1734-IE2V, Series C

Table of Contents

Topic

Page

Important User Information 

2

Environment and Enclosure

3

Preventing Electrostatic Discharge

3

North American Hazardous Location Approval

4

European Hazardous Location Approval

5

Before You Begin

6

Install the Mounting Base

8

Install the Module

9

Install the Removable Terminal Block

10

Wire the Module

12

Communicate with the Module

14

Interpret Status Indicators

15

Specifications

17

Summary of Contents for POINT I/O 1734-IE2C

Page 1: ...Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 North American Hazardous Location Approval 4 European Hazardous Location Approval 5 Before You Begin 6 Install the Mounti...

Page 2: ...ticular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with...

Page 3: ...s to prevent or minimize the spread of flame complying with a flame spread rating of 5VA V2 V1 V0 or equivalent if non metallic The interior of the enclosure must be accessible only by the use of a to...

Page 4: ...le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me son...

Page 5: ...quipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC60529 and used in an environment of not more than Pollution Degree 2...

Page 6: ...Input modules with DeviceNet and PROFIBUS adapters If you are using RSLogix 5000 software version 11 or higher you can also use the modules with ControlNet and Ethernet adapters Use this diagram to id...

Page 7: ...ces 3 Insertable I O module 8 Mechanical keying orange 4 Removable terminal block RTB handle 9 DIN rail locking screw orange 5 Removable terminal block with screw 1734 RTB or spring clamp 1734 RTBS 10...

Page 8: ...module or adapter 3 Press firmly to seat the mounting base on the DIN rail The mounting base snaps into place Be sure that the orange DIN rail locking screw is in the horizontal position and that it h...

Page 9: ...al position You cannot insert the module if the locking mechanism is unlocked 3 Insert the module straight down into the mounting base 4 Press to secure The module locks into place ATTENTION When you...

Page 10: ...s with the wiring base 2 Rotate the terminal block into the wiring base until it locks itself in place 3 If an I O module is installed snap the RTB handle into place on the module WARNING When you con...

Page 11: ...block 3 Press the module lock on the top of the module 4 Pull on the I O module to remove from the base 5 Repeat steps 1 2 3 and 4 for the module to the right 6 Use a small bladed screwdriver to rota...

Page 12: ...ectrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding Module status Network status Status...

Page 13: ...er bus Channel Voltage Input Chassis Ground Common Supply 0 0 2 4 6 1 1 3 5 7 12 24V DC is provided by the internal field power bus In 0 1 0 3 2 5 4 7 6 In 1 Chas gnd C C V V 4 wire In Input channel C...

Page 14: ...Message size 6 Bytes 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Produces scanner Rx Input channel 0 high byte Input channel 0 low byte Input channel 1 high byte Input channel 1 low byte Status by...

Page 15: ...r 2016 Interpret Status Indicators Refer to the following diagram and table for information on how to interpret the status indicators Module status Network status Status of input 0 Status of input 1 4...

Page 16: ...green Device is online but has no connections in the established state Green Device is online and has connections in the established state Flashing red One or more I O connections are in timed out sta...

Page 17: ...bsolute accuracy 1 0 1 Full Scale 25 C 77 F Accuracy drift with temp 30 ppm C 5 ppm C Input update rate per module 120 ms Notch 50 Hz 100 ms Notch 60 Hz default 24 ms Notch 250 Hz 12 ms Notch 500 Hz I...

Page 18: ...ween individual channels Tested to withstand 2550V DC for 60s 50V continuous No isolation between individual channels Tested to withstand 2200V DC for 60s External DC power Supply voltage nom Voltage...

Page 19: ...ged Damp Heat 5 95 noncondensing Vibration IEC60068 2 6 Test Fc Operating 5 g 10 500 Hz Shock operating EC 60068 2 27 Test Ea Unpackaged Shock 30 g Shock nonoperating EC 60068 2 27 Test Ea Unpackaged...

Page 20: ...l Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A and B Ex European Union 2014 34 EU ATEX Directive compliant with EN 60079 0 2012 A11 2013 General Requirements EN 60079 15 2010 Potentia...

Page 21: ...POINT I O 2 Current and 2 Voltage Input Analog Modules 21 Publication 1734 IN027C EN E October 2016 Notes...

Page 22: ...eds to be returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete...