Rockwell Automation Publication 2711P-AP006C-EN-P - November 2018
57
Review the Application Conversion Log
Chapter 4
Screen and Object Conversion Messages
Table 19 lists screen and object messages that may appear in the convert.log file.
Most of the messages identify these attributes for a FactoryTalk View ME
object:
• Screen number and name
• Location (x,y) of the object
• New graphic object name
Use this information to locate the object and make required modifications.
The description for a message may reference a workaround in this document.
Here are some general notes on object conversions:
• Numeric display objects in PanelBuilder32 software are converted to
Text objects with embedded variables in FactoryTalk View ME software.
• A Numeric Input Enable button in FactoryTalk View ME software does
not have a separate display tag. The display value is converted to an
embedded variable on the Label Tab.
• The Numeric Input Cursor object in FactoryTalk View ME software has
a separate indicator tag and does not have a Label tab for text.