1
Publication 2711P-UM001B-EN-P
Chapter
3
Applying Power
Chapter Objectives
This chapter provides information on:
•
wiring and safety guidelines
•
removing and installing power terminal block
•
connecting DC power
•
connecting AC power
•
resetting the terminal
•
startup sequence
Wiring and Safety
Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for
Employee Workplaces when wiring the PanelView Plus terminals. In
addition to the NFPA guidelines:
•
connect the terminal and other similar electronic equipment to
its own branch circuit.
•
protect the input power by a fuse or circuit breaker rated at no
more than 15 Amps.
•
route incoming power to the terminal by a separate path from
the communication lines.
•
where power and communication lines must cross, they should
cross at right angles.Communication lines can be installed in the
same conduit as low level DC I/O lines (less than 10 volts).
•
shield and ground cables appropriately to avoid Electromagnetic
Interference (EMI). Grounding minimizes noise from EMI and is
a safety measure in electrical installations.
For additional grounding recommendations, refer to the National
Electrical Code published by the National Fire Protection Association
of Boston.
Summary of Contents for PanelView Plus 2711P
Page 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Page 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Page 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Page 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Page 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Page 169: ...AB Drives...