Terminal Connections
6-15
Remote I/O Connections
To connect a PanelView Plus terminal to a Remote I/O scanner, use
cable Catalog No. 1770-CD (equivalent to Belden 9463). The
maximum cable length (link distance) is determined by the baud rate.
•
2,800 meters (10,000 feet) for 57.6K baud
•
1,400 meters (5,000 feet) for 115.2K baud
•
700 meters (2,500 feet) for 230.4K
See Programmable Controller Wiring and Grounding Guidelines,
Publication 1770-4.1. The user manual for the I/O scanner module
also provides cabling information.
The orientation of the Remote I/O Connector on the PanelView Plus is
reversed from the PLC Scanner connector. However, the polarity is the
same as the scanner card connection to the SLC.
Logic Controller or
Scanner Remote I/O Port
PanelView Plus 700-1500
82 or 150 Ohm Terminating Resistor
Blue 1
Shield SH 2
Clear 3
Clear 3
Shield SH 2
Blue 1
Belden
Ferrite
PanelView Plus 400-600
Logic Controller or
Scanner Remote I/O Port
Clear = 2
Shield
Blue = 1