Allen-Bradley PanelView 2711P-RW1 Installation Instructions Manual Download Page 1

Installation Instructions

Original Instructions

PanelView Plus 700 to 1500 and PanelView 
Plus Compact 1000 Terminals and Display 
Modules

Catalog Numbers 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-
T10C4D1

Summary of Changes

This document contains new and updated information as indicated in the following table. 

Topic

Page

Summary of Changes

1

Important User Information

2

About This Publication

3

Hazardous Locations

5

Wiring and Safety Guidelines

8

About the PanelView Plus 700 to 1500 Terminals

9

Parts List

10

Required Tools

10

Install the Terminal

11

DC Power Connections

17

AC Power Connections

21

Battery Precautions

23

Troubleshooting

25

Specifications

29

Additional Resources

31

Topic

Page

Updated the Attention note in the section titled External Power Supply for Nonisolated DC Terminals and in the 
section titled External Power for Isolated DC Terminals.

18

Summary of Contents for PanelView 2711P-RW1

Page 1: ...Changes 1 Important User Information 2 About This Publication 3 Hazardous Locations 5 Wiring and Safety Guidelines 8 About the PanelView Plus 700 to 1500 Terminals 9 Parts List 10 Required Tools 10 I...

Page 2: ...d by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written...

Page 3: ...s instructions on how to install these devices in a panel Factory assembled PanelView Plus or PanelView Plus CE 700 to 1500 terminals PanelView Plus or PanelView Plus CE 700 to 1500 display modules Fa...

Page 4: ...d to take caution in this regard This equipment is supplied as open typeequipment It mustbemounted within anenclosure that is suitably designed for those specific environmental conditions that will be...

Page 5: ...code of T4 when operating in a 55 C 131 F maximum ambient temperature Do not install the terminals in environments where atmospheric gases have ignition temperatures less than 135 C 275 F Explosion Ha...

Page 6: ...T4 pour une temp rature ambiante maximale de 55 C N installez pas les terminaux dans des environnements contenant des gaz atmosph riques inflammables moins de 135 C DANGER D EXPLOSION La substitution...

Page 7: ...National Electrical Code article 500 Terminals Control Drawing Selected nonincendive field wiring apparatus must have nonincendive circuit parameters conforming with Table 2 Table 1 PanelView Plus USB...

Page 8: ...er associated nonincendive field wiring apparatus WiringandSafetyGuidelines Use publication NFPA 70E Electrical Safety Requirements for Employee Workplaces IEC 60364 Electrical Installations in Buildi...

Page 9: ...us700to1500Terminals The PanelView Plus terminals have these modular components Display module 700 1000 1250 and 1500 Logic module with AC or DC power CompactFlash card slot Ethernet port serial port...

Page 10: ...ly The PanelView Plus Compact 1000 terminal has these features 1000 touch screen display module USB ports 2 RS 232 serial port 10 100Base T Ethernet port Power input 24V DC non isolated CompactFlash T...

Page 11: ...e between 0 55 C 32 131 F These minimum clearances are required for ventilation Top clearance 51 mm 2 in Bottom clearance 102 mm 4 in Side clearances 25 mm 1 in Back clearance 25 mm 1 in Minimum side...

Page 12: ...properly positioned on the terminal This gasket forms a compression type seal Do not use sealing compounds 3 Install the legend strips before installing the terminal if you are using keypad legend st...

Page 13: ...niformly 7 Tighten the mounting clip screws to a torque of 0 90 1 1 N m 8 10 lb in by using the specified torque sequence making sure not to overtighten Tighten the mounting clips to the specified tor...

Page 14: ...mpact 1000 touch only terminals The other size terminals look similar Measurements are in mm in Terminal Type Height Approx mm in Width Approx mm in Depth Approx mm in 700 Keypad or Keypad and Touch 1...

Page 15: ...0 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 1000 Terminal Dimensions Keypad or Keypad Touch Touch Screen a 55 2 18 Display to Logic Module b 83 3 27 Display to Comm Module...

Page 16: ...minal block for ease of installation wiring and maintenance Series A to D DC logic modules use a 3 position terminal block Series E or later DC logic modules use a 2 position terminal block All logic...

Page 17: ...ve an integrated 24V DC power supply Both isolated and non isolated power supplies have these ratings 24V DC nominal 18 32V DC 70 W maximum 2 9 A at 24V DC The power supply is internally protected aga...

Page 18: ...lated DC logic modules refer to the PanelView Plus Terminals User Manual publication 2711P UM001 Use a safety extra low voltage SELV or protective extra low voltage PELV power supply as required by lo...

Page 19: ...ed and non isolated communication ports For more information refer to the PanelView Plus Terminals User Manual publication 2711P UM001 IMPORTANT The earth ground connection to ground is mandatory This...

Page 20: ...and the terminal for proper connections 3 Secure the earth ground wire to the earth ground terminal screw at the bottom of the display DC Power Supply Connections ExplosionHazard Donotdisconnectequipm...

Page 21: ...Wire Specifications for AC Input Power Terminal Block Wire Type Dual wire Gauge 1 1 Two wire max per terminal Single wire Gauge Terminal Screw Torque Stranded or solid Cu 90 C 194 F 22 16 AWG 22 14 A...

Page 22: ...rth ground wire to the functional earth ground screw on the back of the display to ground bus 5 Apply AC power to the terminal Explosion Hazard Do not connect or disconnect equipment while circuit is...

Page 23: ...board When you connect or disconnect the battery anelectrical arc can occur This could cause an explosion in hazardous locationinstallations Be sure that poweris removed and the area is nonhazardousbe...

Page 24: ...f the battery 8 Insert the new battery 9 Reattach the logic module by aligning the two connectors on the bottom of the module with the connectors on the terminal 10 Push down on the logic module until...

Page 25: ...ation FAULT indicator red for hardware faults When the terminal starts the fault indicator should be off except for a few brief flashes and the comm indicator on If the indicators remain off the power...

Page 26: ...guration mode on the terminal access Terminal Settings Display Screen Saver Indicator States If the Terminal Stops During Startup Fault Red Indicator Comm Green Indicator Description Blinking 1 1 Blin...

Page 27: ...hecks the integrity of the battery hardware 2 5 Registry Search Locatesandloadsthemostrecent validregistry Multiplecopiesoftheregistryare maintained If power is lost during a registry update a valid r...

Page 28: ...the logic module 30 Watchdog Test Watchdog test failure Reload the firmware If error persists replace the logic module 31 Stuck Key Function key failure Check that nothing is pressed against a key Res...

Page 29: ...ical Input voltage DC 24V DC nom 18 32V DC Power consumption DC 70 W max 2 9 A 24V DC 39 W typical 1 6 A 24V DC Input voltage AC 85 264V AC 47 63 Hz Power consumption AC 160VA max 65VA typical PCI slo...

Page 30: ...ears min at 25 C 77 F Clock Battery backed 2 minutes per month Status indicators COMM green Fault red Application flash memory 700 to 1500 series D or earlier logic modules 2711P RW1 2711P RW2 2711P R...

Page 31: ...ustrial Emissions CE LVD EN61131 2 Programmable Controllers C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Marine Products identified with the suffix M i...

Page 32: ...Tel 90 216 5698400 Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product...