Valid Addressing Modes and File Types for Instruction Parameters
C–13
Instruction
Description
Instruction
Parameter
Valid Addressing
Mode(s)
Valid File Types
Valid Value
Ranges
SUS
Suspend
suspend ID
immediate,
–32,768–32,767
TND
Temporary End
Not Applicable
TOD
Convert to BCD
source
direct, indexed direct
O, I, S, B, T, C, R, N
destination
direct
O, I. S. B. T, C, R, N
Not Applicable
TOF
Timer Off-Delay
timer
direct
T (element level)
Not Applicable
time base
immediate
0.01 or 1.00
preset
(contained in the
timer register)
0–32,767
accum
(contained in the
timer register)
0–32,767
TON
Timer On-Delay
timer
direct
T (element level)
Not Applicable
time base
immediate
0.01 or 1.00
preset
(contained in the
timer register)
0–32,767
accum
(contained in the
timer register)
0–32,767
XIC
Examine if Closed
source bit
direct
O, I, S, B, T, C, R, N
(bit level)
Not Applicable
XIO
Examine if Open
source bit
direct
O, I, S, B, T, C, R, N
(bit level)
Not Applicable
XOR
Exclusive OR
address A
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,767
address B
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,767
destination
direct, indexed direct
O, I, S, B, T, C, R, N
Not Applicable
Reference