5.

 

Add Output power jumpers to Micro850 PLC  

 

6x 6” Red 16GA Wire provided in kit 

6.

 

Move Upper Horizontal Wire Way Up for Clearance 

 

Remove Wire Way from Back Panel 

 

Mark new holes ¼” above the old holes 

 

Drill and Tap holes for 8-32 screws used to hold the Wire Way 

 

Attach Wire Way to Back Panel 

7.

 

Re-Connect wires that were removed from ML1000 PLC to Micro850 PLC 

 

Micro850 PLC has removable Screw Terminals for Inputs and Outputs. This feature 
makes it easier to remove them from the PLC while reconnecting all of the inputs and 
outputs. 

8.

 

Replace 250mA fuse (7FU) with 5A fuse provided in kit  

 

Reviews: