68
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Chapter 5
Communication Connections
3.
Specify the following parameters:
•
Baud rate
•
Parity
•
Unit address
•
Modbus Role (Master, Slave, Auto)
4.
Click Advanced Settings to set advanced parameters.
Refer to the table for available options and default configuration for
advanced parameters.
Configure ASCII
1.
Open your Connected Components Workbench project. On the device
configuration tree, go to Controller properties. Click Serial Port.
Modbus RTU Parameters
Parameter
Options
Default
Baud Rate
1200, 2400, 4800, 9600, 19200, 38400
19200
Parity
None, Odd, Even
None
Modbus Role
Master, Slave, Auto
Master
Modbus RTU Advanced Parameters
Parameter
Options
Default
Media
RS-232, RS-232 RTS/CTS, RS-485
RS-232
Data bits
Always 8
8
Stop bits
1, 2
1
Response timer
0…999,999,999 milliseconds
200
Broadcast Pause
0…999,999,999 milliseconds
200
Inter-char timeout
0…999,999,999 microseconds
0
RTS Pre-delay
0…999,999,999 microseconds
0
RTS Post-delay
0…999,999,999 microseconds
0
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...