Appendix F
PID Function Blocks
Troubleshooting an
Autotune Process
You can tell what is going on behind the autotune process from the sequences of
control output. Here are some known sequences of control output and what it
means if autotune fails. For the ease of illustrating the sequence of control output,
we define:
Load: 50
Step: 20
PID Application Example
The illustration above shows a basic water level control system, to maintain a
preset water level in the tank. A solenoid valve is used to control incoming water,
filling the tank at a preset rate. Similarly, outflowing water is controlled at a
measureable rate.
Output Sequence 1: 50 -> 70 -> 30
Sequence Condition
Autotune Result
Action for Autotune Fail
Process value reached 'first peak' and
'second' peak in time
Likely successful
NA
Output Sequence 2: 50 -> 70 -> 50
Sequence Condition
Autotune Result
Action for Autotune Fail
Process value not able to reach
'first peak'
Likely unsuccessful
Reduce Deviation or Increase Step
Output Sequence 3: 50 -> 70 -> 30 -> 50
Sequence Condition
Autotune Result
Action for Autotune Fail
Process value not able to reach
second peak
Likely unsuccessful
Increase Deviation or increase Step
Output Sequence 4: 50 -> 70
Sequence Condition
Autotune Result
Action for Autotune Fail
Process value not able to reach First
peak in time
Likely unsuccessful
Increase ATDynamSet
Water In
Water Level
Tank
Water Out
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...