Connect the Kinetix 5700 Drive System
Chapter 5
Ground the System Subpanel
Ground Kinetix 5700 power supplies, inverters, and capacitor modules to a
bonded cabinet ground bus with a braided ground strap. Keep the braided
ground strap as short as possible for optimum bonding.
Figure 62 - Connect the Ground Terminal
Refer to the System Design for Control of Electrical Noise Reference Manual,
publication
, for more information.
MBRK
+
-
D+
D-
MF
Braided Ground Straps
12 mm (0.5 in.) by 0.8 mm (0.03 in.).
Keep straps as short as possible.
4
3
2
1
DC-bus Power Supply
(typical example)
Kinetix 5700 Drive System
(typical system)
Item
Description
1
Ground screw (green) 2.0 N•m (17.7 lb•in), max
2
Braided ground strap (customer supplied)
3
Ground grid or power distribution ground
4
Bonded cabinet ground bus (customer supplied)