Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
45
Plan the Kinetix 5700 Drive System Installation
Chapter 2
Table 11 - iTRAK Power Supply
Table 12 - Capacitor Module
Table 13 - Extension Module
Noise Reduction Guidelines for Drive System Accessories
Refer to this section when mounting an AC (EMC) line filter or external shunt
resistor for guidelines designed to reduce system failures caused by excessive
electrical noise.
AC Line Filters
Observe these guidelines when mounting your AC (EMC) line filter (refer to
the figure on
for an example):
• Mount the AC line filter on the same panel as the Kinetix 5700 power
supply and as close to the power supply as possible.
• Good HF bonding to the panel is critical. For painted panels, refer to
the examples on
• Segregate input and output wiring as far apart as possible.
Wire/Cable
Connector
Zone
Method
Very Dirty
Dirty
Clean
Ferrite Sleeve
Shielded Cable
DC-/DC+ (DC bus)
DC
Bus-bar only, no wiring connector.
iTRAK DC-bus output A and B
IDC
X
X
24V DC control input power
CP
X
X
iTRAK 24V DC control output power A and B
ICP
iTRAK digital inputs
IOD
X
iTRAK ready output
IR
X
Ethernet
PORT1
PORT2
X
X
Wire/Cable
Connector
Zone
Method
Very Dirty
Dirty
Clean
Ferrite Sleeve
Shielded Cable
DC-/DC+ (DC bus)
DC
Bus-bar only, no wiring connector.
DC-/DC+ (shielded extension)
M8 Stud
X
24V DC
CP
X
Module status
MS
X
Wire/Cable
Connector
Zone
Method
Very Dirty
Dirty
Clean
Ferrite Sleeve
Shielded Cable
DC-/DC+ (DC bus)
DC
Bus-bar only, no wiring connector.
DC-/DC+ (shielded extension)
M8 Stud
X