Chapter 2
Behavior models used in CIP Motion
54
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018
Current State
Event
Conditions
Next State
Starting
Disable
Stopping
Starting
Start Complete
In Process = 0
Running
Starting
Start Complete
In Process = 1
Testing
Stopping
Stop Complete
Shutdown = 0
Stopped
Stopping
Stop Complete
Shutdown = 1
Shutdown
Stopping
Major Fault
Aborting
Stopping
Enable
Flying Start Enable = 1
Starting
Aborting
Stop Complete
Major Faulted
Aborting
Fault Reset
Stopping
Testing
Shutdown
Stopping
Testing
Major Fault
Aborting
Testing
Disable
Stopping
Testing
Test Complete
Stopping
Running
Shutdown
Stopping
Running
Major Fault
Aborting
Running
Disable
Stopping
Any State
Connection Close
Initializing
Any State
Connection Loss
Major Faulted
*
Event disables the axis power structure after a Category 2 Stop leaves the axis in active hold condition.
See also
When the Motion Control Axis is not actively controlling axis motion (Control
Mode = No Control), the state diagram reduces to the following for a Feedback
Only axis or CIP Motion Encoder device type. Shaded regions show mapping of
Axis States to corresponding Identity Object states. State transitions terminating
on shaded boxes can transition to any axis state within the box.
Feedback Only Axis Behavior
Model