Troubleshoot the Kinetix 5100 Drive System
Chapter 16
Drive Stopping Behavior
A fault (code E
nnn
) triggers the shutdown (servo off ) behavior of the drive.
Parameter ID675 (P1.032), MotorStopMode, configures the drive stopping
behavior.
Clear Faults
The two methods for clearing faults depends on the type.
Warnings (A
nnn
): When the condition that caused the warning is corrected, the
warning clears automatically.
Faults (E
nnn
): Clear the fault by one of the following methods:
• For a major unrecoverable fault, cycle power to clear the fault. If the issue
persists, contact your distributor or Rockwell Automation representative.
• For a major recoverable fault:
– Click Reset Module in the Studio 5000 Logix Designer software. For
more information, see
Fault and Status Information in Studio 5000
– By using the DI.ARST signal.
– By clicking Fault Reset in the Fault Information dialog of the
KNX5100C software (see
Fault Information in the KNX5100C
).
– Set ID101 (P0.001) FltWarnCode to 0.
– By using the raC_Dvc_K5100_MAFR add-on instruction in the
Studio 5000 Logix Designer software (for more information on add-on
instructions, see
).
General Troubleshooting
The following conditions do not always result in a fault code, but can require
troubleshooting to improve performance.
MotorStopMode Setting
Drive Behavior
0000 (default)
Dynamic brake stop
0010
Disable and coast
0020
Use dynamic brake first, then let the motor run freely once the speed is slower
than the value of parameter ID145 (P1.038), ZeroSpeedWindow.