34
Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Chapter 3
Kinetix 350 Drive Connector Data
Kinetix 350 Drive Connectors
and Indicators
Although the physical size of the Kinetix® 350 drives vary,
the location of the
connectors and indicators is identical.
Figure 10 - Kinetix 350 Drive Connector and Indicators
Table 12 - Kinetix 350 Drive Connectors
Item
Description
Item
Description
1
Mains (IPD) connector
9
Motor feedback (MF) connector
2
Data status indicator and diagnostic display
10
Ground lug
3
Memory module socket
11
Shunt resistor and DC bus (BC) connector
4
Network status indicator
12
Back-up power (BP) connector
5
Module status indicator
13
Display control push buttons (3)
6
Axis status indicator
14
Motor power (MP) connector
7
Ethernet communication port (Port 1)
15
Safe torque-off (STO) connector
8
I/O (IOD) connector
10
3
4
2
5
6
7
9
8
1
12
13
11
14
15
10
0
3 5 0
Kinetix® 350 Drive, Front View
(2097-V33PR5-LM drive is shown)
Kinetix 350 Drive, Bottom View
(2097-V33PR5-LM drive is shown)
Kinetix 350 Drive, Top View
(2097-V33PR5-LM drive is shown)
Designator
Description
Connector
IPD
AC input power
3-position or 4-position plug/header
PORT1
Ethernet communication port
RJ45 Ethernet
IOD
I/O
SCSI 50-pin high-density connector
MF
Motor feedback
15-pin high-density D-shell (male)
BP
Back-up power
2-pin quick-connect terminal block
BC
Shunt Resistor and DC Bus
7-pin quick-connect terminal block
MP
Motor power
6-pin quick-connect terminal block
STO
Safe torque off (STO) Terminal
6-pin quick-connect terminal block