Publication 1753-RM002C-EN-P - September 2008
Appendix A
Specifications
Climatic Conditions
The most important parameters and tests for climatic conditions are
listed in the following table.
Mechanical Conditions
The most important parameters and tests for mechanical conditions
are listed in the following table.
IEC/EN 61131-2
Paragraph
6.3.4
Climatic Tests
Temperature operating
0…60 °C (32…140 °F) (Test limits -10…70 °C (14…158 °F))
Storage Temperature
-40…85 °C (-40…185 °F)) (Battery only -30 °C (-22 °F))
6.3.4.2
Dry heat and cold resistance test
(70 °C / -25 °C (158 °F/-13 °F), 96h, EUT Power supply unconnected)
6.3.4.3
Change of temperature, resistance and immunity test
(-25 °C / 70 °C (-13 °F/158 °F), EUT Power supply unconnected and
0 °C / 55 °C (32 °F/131 °F), EUT)
6.3.4.4
Cyclic damp heat resistance test
(25 °C / 55 °C (77 °F/131 °F), 95% relative humidity, EUT power supply
unconnected)
IEC/EN 61131-2
Paragraph 6.3.5
Mechanical Tests
Vibration test operating
5…9 Hz/3.5 mm
9…150 Hz/1g
6.3.5.1
Immunity vibration test (10…150 Hz, 1g,
EUT operating, 10 cycles per axis)
6.3.5.2
Immunity shock test (15g, 11 ms, EUT operating,
2 cycles per axis)
Summary of Contents for GuardPLC 1753
Page 4: ...4 Publication 1753 RM002C EN P September 2008 Summary of Changes...
Page 8: ...8 Publication 1753 RM002C EN P September 2008 Table of Contents...
Page 12: ...12 Publication 1753 RM002C EN P September 2008 Preface...
Page 84: ...84 Publication 1753 RM002C EN P September 2008 Chapter 7 GuardPLC Controller Operating System...
Page 106: ...106 Publication 1753 RM002C EN P September 2008 Chapter 9 Configuring Communication...
Page 114: ...114 Publication 1753 RM002C EN P September 2008 Appendix B Use in Central Fire Alarm Systems...
Page 118: ...118 Publication 1753 RM002C EN P September 2008 Index...
Page 119: ...Allen Bradley Parts...