Chapter 5
Add, Configure, Monitor, and Replace CIP Safety I/O Devices
Set the Advanced Connection Reaction Time Limit Parameters
Configure connection parameters like the timeout multiplier and network
delay multiplier on the Advanced Connection Reaction Time Limit dialog
box.
Figure 21 - Advanced Configuration
Timeout Multiplier
The Timeout Multiplier determines the number of RPIs to wait for a packet
before declaring a connection timeout. This translates into the number of
messages that can be lost before a connection error is declared.
For example, a timeout multiplier of 1 indicates that messages must be received
during each RPI interval. A Timeout Multiplier of 2 indicates that 1 message
can be lost as long as at least 1 message is received in 2 times the RPI (2 x RPI).