Publication 1794-6.5.11 - November 1997
2-10
How to Install Your Frequency Input Module
Connecting Wiring using a 1794-TB3G and –TB3GS Terminal
Base Units
1. Connect the individual signal wiring to the proper numbered
terminals on the 0-15 row (A) and 16-33 row (B) on the terminal base
unit. Connect the inputs as shown in the table on page 1.
2. Connect output signal and supply wiring to the numbered
terminals on rows B and C, as shown in the wiring connection on
page 1.
3. Terminate shields to terminals 16 or 33 on row B, or 40 through 45 on
row C.
4. Connect
+
24V dc to terminal 34 on the 34-51 row (C), and 24V
common to terminal 35 on the 34-51 row (C).
5. If daisy chaining the
+
24V dc power to the next 1794-TB3G or
-TB3GS base unit, connect a jumper from terminal 50 (
+
24V) on this
base unit to terminal 34 and from terminal 51 (24V dc common) to
terminal 35 on the next 1794-TB3G or -TB3GS base unit.
NOTE: Use extreme care when connecting wiring to an adjacent terminal
base unit. Wiring for the 1794-TB3G and -TB3GS terminal base units is
different from other 1794 terminal base units.
!
ATTENTION: To reduce susceptibility to noise, power
frequency modules and digital modules from separate power
supplies. Do not exceed a length of 33 ft (10m) for dc power
cabling.
!
ATTENTION: Do not daisy chain power or ground from
the 1794-TB3G or -TB3GS terminal base unit to any ac or
dc digital module terminal base unit.
!
ATTENTION: This module does not receive power from
the backplane.
+
24V dc power must be applied to your
module before operation. If power is not applied, the module
position will appear to the adapter as an empty slot in your
chassis. If the adapter does not recognize your module after
installation is completed, cycle power to the adapter.