Publication 1794-6.5.11 - November 1997
2-2
How to Install Your Frequency Input Module
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage,
by applying the safety requirements of EN 61131-2 Programmable
Controllers, Part 2 – Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
•
Industrial Automation Wiring and Grounding Guidelines For Noise
Immunity, publication 1770-4.1
•
Guidelines for Handling Lithium Batteries, publication AG-5.4
•
Automation Systems Catalog, publication B111
This equipment is classified as open equipment and must be mounted in
an enclosure during operation to provide safety protection.
Power Requirements
The wiring of the terminal base unit is determined by the current draw
through the terminal base. Make certain that the current draw does not
exceed 10A.
The frequency input module requires 30mA at 5V dc from the flexbus
backplane.
!
ATTENTION: Total current draw through the terminal
base unit is limited to 10A. Separate power connections may
be necessary.