Publication 1784-6.5.30 - February 2001
Using IOLinx To Test the Example Network
5-7
Testing the RediSTATION and Photoeye Inputs
Click on the I/O tab to view the 1784-PCIDS card’s input and output
image tables. The contents of the tables are shown as hexadecimal
numbers.
Recall from chapter 5 that the RediSTATION inputs are mapped as
follows:
START: Word 0, bit 1
STOP: Word 0, bit 0
The photoeye input is mapped to:
Word 0, bit 8
1.
Use the
Switch Mode
button to change the scanner’s mode from
IDLE
to
RUN
.
2.
Repeatedly press and release the
START
button on the
RediSTATION. On your screen, you should see input byte 0
changing back and forth from “0” to “2” as bit 1 sets and resets
when you press and release the button.
3.
Repeatedly press and release the
STOP
button on the
RediSTATION. On your screen, you should see input byte 0
changing back and forth from “0” to “1” as bit 0 sets and resets
when you press and release the button.
Addresses are also
in hexadecimal
One byte shown in
hexadecimal
Summary of Contents for DeviceNet 1784-PCIDS
Page 1: ...DeviceNet PCI Communication Interface Card 1784 PCIDS CPCIDS User Manual Allen Bradley Parts...
Page 4: ......
Page 12: ...Publication 1784 6 5 30 February 2001 P 8 About This User Manual...
Page 38: ...Publication 1784 6 5 30 February 2001 3 8 Setting Up the Hardware for the Example Network...
Page 58: ...Publication 1784 6 5 30 February 2001 4 20 Configuring the DeviceNet Network...
Page 68: ...Publication 1784 6 5 30 February 2001 5 10 Using IOLinx To Test the Example Network...
Page 82: ...Publication 1784 6 5 30 February 2001 B 12 Creating and Running a SoftLogix 5 Application...
Page 94: ...Publication 1784 6 5 30 February 2001 D 2 Changing the Network Baud Rate...
Page 99: ...Allen Bradley Parts...
Page 101: ...DeviceNet PCI Communication Interface Card User Manual Allen Bradley Parts...