1761-6.5
5-8
DNI Configuration Parameters and Programming Notes
Output Size
This parameter identifies the size, in words, of the data array that will be
written to the controller attached to the DNI’s RS-232 port. The array may
contain up to 16 (16-bit) words of data for DNI Series A (32 words for DNI
Series B) from a contiguous block within the attached controller.
The first byte (byte 0) of the first word contains the status byte and is not
available to the user. A sample of the data array is shown below:
Parameter
Type
Parameter Number
Description Range
Default Value
Series A Series B
I/O
8
6
Output Size
Series A: 1 to 16
Series B: 1 to 32
1
Important:
For DNI Series B, you must also configure the Output Split
Point. See page 5-9.
Word
Output Image
Series A Series B
0
0
Data (8 bits)
Status
1
1
Data Most Significant Byte (MSB) Data Least Significant Byte (LSB)
2
2
Data MSB
Data LSB
3
3
Data MSB
Data LSB
↓
↓
↓
↓
14
30
Data MSB
Data LSB
15
31
Data MSB
Data LSB
Note:
Byte 1 (MSB) of word 0 is available for user data.
Note:
For information on the Status Byte (byte 0), see the Status Byte
section on page 5-23.
Summary of Contents for DeviceNet 1761-NET-DNI
Page 14: ...1761 6 5 P 6...
Page 16: ...1761 6 5 1 2 Product Overview...
Page 22: ...1761 6 5 2 6 Quick Start for Experienced Users...
Page 34: ...1761 6 5 4 6 Installation and Wiring...
Page 74: ...1761 6 5 6 16 Setup Programming and T roubleshootin g...
Page 84: ...1761 6 5 7 10 Application Examples...
Page 94: ...1769 6 5 A 4 Specifications...
Page 99: ...1761 6 5 I 3 AB Parts...
Page 100: ......